Viessmann VITOSOLIC 200 Manuel d'installation

Naviguer en ligne ou télécharger Manuel d'installation pour Accessoires pour piscines hors sol Viessmann VITOSOLIC 200. Viessmann VITOSOLIC 200 Unit installation Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 62
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
VITOSOLIC 200
Installation and
Service Instructions
for use by heating contractor
Vitosolic 200
Electronic temperature differential control unit for solar heating systems
LR 102874
Read and save these instructions
for future reference.
IMPORTANT
Please file in Service Binder
5285 965 v1.2 08/2006
Vue de la page 0
1 2 3 4 5 6 ... 61 62

Résumé du contenu

Page 1 - Service Instructions

VITOSOLIC 200Installation andService Instructionsfor use by heating contractorVitosolic 200Electronic temperature differential control unit for solar

Page 2 - IMPORTANT

10System designsSystem design 2 (cont.)Item DescriptionDHW tank heating by solar energy1 Vitosolic 2002 Collector temperature sensor3 Tank temperature

Page 3

11System designsSystem design 3Dual mode DHW heating and heating backup via a buffer tankDHW heating without solar energyThe upper indirect coil of th

Page 4 - ¨ Safety instructions

12System designsSystem design 3 (cont.)The pump will be switched OFF if the actual temperaturefalls below shut-down temperature differential ΔT5off.Th

Page 5 - System design 1

13System designsSystem design 3 (cont.)Main menu>Solar>ContractorContractorFactory default setting Modified totstopLength of pump run interrupti

Page 6 - System design 1 (cont.)

14System designsSystem design 3 (cont.)A Solar panelB Solar-DiviconC Solar pump lineD Draw-off pointsE DHW circulationF DHW circulation output of boil

Page 7

15System designsSystem design 3 (cont.)ItemDescriptionDHW tank heating by solar energy1 Vitosolic 2002 Collector temperature sensor3 Tank temperature

Page 8 - System design 2

16System designsSystem design 4Dual mode DHW heating with two DHW tanks(particularly suitable for retrofitting in existing systems)DHW heating without

Page 9

17System designsSystem design 4 (cont.)Main menu>System>OptionsOptionsFactory default setting Change toΔTFct6ΔT function for controlling circula

Page 10 - System design 2 (cont.)

18System designsSystem design 4 (cont.)Installation diagram 4(System with two DHW tanks with indirect coils)A Solar panelB Solar-DiviconC Draw-off poi

Page 11 - System design 3

19System designsSystem design 4 (cont.)Item DescriptionHeating DHW tank 1 through solar energy1 Vitosolic 2002 Collector temperature sensor3 Tank temp

Page 12 - System design 3 (cont.)

2General informationSafety, Installation and Warranty requirementsPlease ensure that this manual is read and understood before commencing installation

Page 13

20System designsSystem design 5Dual mode DHW and swimming pool heatingDHW heating without solar energyThe top part of the DHW tank is heated by the bo

Page 14

21System designsSystem design 5 (cont.)SettingsMain menu>Operator code>Set to 200Main menu>Solar>OptionsSystem>Set to 3Hyd. type>Set

Page 15

22System designsSystem design 5 (cont.)Main menu>Solar>ContractorContractorFactory default setting Change totstopLength of pump run interruption

Page 16 - System design 4

23System designsSystem design 5 (cont.)Main menu>System>Setting valuesSetting valuesFactory default setting Modified toTh2onset same value as fo

Page 17 - System design 4 (cont.)

24System designsSystem design 5 (cont.)A Solar panelB Solar-DiviconC Solar pump lineD Draw-off pointsE DHW circulationF DHW circulation output of boil

Page 18

25System designsSystem design 5 (cont.)*1Start-up signal for filter system with pump qU.*2In conjunction withViessmann Trimatik:Connection to termina

Page 19

26System designsSystem design 5 (cont.)Item DescriptionDHW tank heating by solar energy1 Vitosolic 2002 Collector temperature sensor3 Tank temperature

Page 20 - System design 5

27Installation and connectionsControl unit installationInstallation locationNear the DHW tank, observing the electric connections or their cable/lead

Page 21 - System design 5 (cont.)

28Installation and connectionsSummary of electrical connectionsA Control Unit connection chamberB Printed Circuit BoardC Sensor inouts for Pt 500D Sol

Page 22

29Installation and connectionsActuators (pumps and valves)InstallationThe Solar-Divicon pump station includes the solarloop circulation pump.Alternati

Page 23

3IndexIndexSystem designsGeneral notes 4...

Page 24

30Installation and connectionsFixed high limit (cont.)ConnectionThree-conductor cable AWG 14.A Printed circuit boardB Fixed high limitC Solar circuit

Page 25

1.3.2.A31Installation and connectionsSolar cellInstallationSeparate installation instructionsThe solar cell is marked with a letter which must be ente

Page 26

32Installation and connectionsSensors (cont.)Additional tank temperature sensorsInstallationPlease note:Never wrap insulating tape around sensor.Seal-

Page 27 - Control unit installation

145231GNDS1S2S3S4S5S6S7S8S9S10S11S12CS10----Imp1Imp2145AB33Installation and connectionsKM BUS connectionConnections with Vitotronic control units via

Page 28 - 5285 965 v1.2 08/2006

34Installation and connectionsPower supplyRegulationsCarry out the power supply and all grounding (e.g. fault current circuit) in accordance with loca

Page 29 - Fixed high limit

35CommissioningMenu structure summary – Main menuThe complete menu structure of the control unit is shown in the following summary. Subject to system

Page 30 - Fixed high limit (cont.)

36CommissioningMenu structure summary – SolarMain menu > Solar*1Influences the control characteristics of the solar circuit pump and the secondary

Page 31 - Tank temperature sensor

37CommissioningMenu structure summary – SystemMain menu > System*1Time window adjustment, see page 59.5285 965 v1.2 08/2006ContractorOptionsSetting

Page 32 - Sensors (cont.)

38CommissioningMenu structure summary – HMMain menu > HMMenu structure summary – ContractorMain menu > Contractor*1Like HM1.*2Setting Heat trans

Page 33 - KM BUS connection

39CommissioningStepsPage1. Probes or sensors correctly inserted into sensor wells? 31...

Page 34 - Power supply

4System designsGeneral notesOver the following pages, the methods of operation havebeen described, and the installation has been depicted asdifferent

Page 35

40CommissioningFurther details regarding individual stepsCommissioning the control unit1. Apply power to the control. The operating lampilluminates gr

Page 36 - Commissioning

41CommissioningFurther details regarding individual steps (cont.)With extension kitThe energy statement is calculated from the temperaturedifferential

Page 37

42Service scansScanning temperatures and operating conditionsSubject to system version, you can scan the following values:1. Main menu>Actual value

Page 38 - Menu structure summary – HM

43Service scansScanning temperatures and operating conditions (cont.)2. Main menu>Solar>StatementPlain textDescription UnitSolar statement:Colma

Page 39

44TroubleshootingFault messagesFaults are indicated by the operating lamp (flashes red) and may be scanned:Main menu>ReportsReportsCause RemedyNo f

Page 40

45TroubleshootingChecking sensors1. Disconnect the relevant sensor and measure theresistance.Temperaturein °C/ °FResistancein Ω20/6840/10450/12260/140

Page 41 - Relay test

46Function descriptionsSummary of additional functionsFurther functions may be added to each system design.Functions for which the same relay output i

Page 42

47Function descriptionsSummary of additional functions (cont.)Main menu>System>OptionsPlease note:Select ”Yes” to activate the required function

Page 43 - Scanning heat volume

48Function descriptionsSummary of system parametersThese values can only be adjusted if the respective function is activated.Main menu>Solar>Set

Page 44 - Fault messages

49Function descriptionsSummary of system parameters (cont.)DisplaytextDescription Factory defaultsettingSetting range Set toTcolsetSet collector tempe

Page 45 - Changing the fuse

5System designsSystem design 1Dual-mode DHW heating with Vitocell-B 100 or Vitocell-B 300 DHW tanksDHW heating without solar energyThe upper indirect

Page 46 - ”Sens. Ext. HE”

50Function descriptionsBypass (cont.)Version 2 – Bypass control with solar cell and collector temperature sensorVitosolic 200 measures the radiation i

Page 47

51Function descriptionsExternal heat exchangerThe selected relay switches the consumer ON if the set start-up temperature differential is exceeded, an

Page 48 - Summary of system parameters

52Function descriptionsFrost protectionAt a collector temperature below +4 °C / 39 °F, the solar circuit pump will be started to prevent collector dam

Page 49

53Function descriptionsSuppression of reheating by boiler (cont.)Systems with additional Viessmann control unitsReheating of the DHW tank by the boile

Page 50 - Bypass (cont.)

54Function descriptionsSuppression of reheating by boiler (cont.)Tank temperature sensor as NTC (For Vitodens)A Vitosolic 200B Printed circuit boardC

Page 51 - Return cooling function

55Function descriptionsTank loadingThis function is achieved via thermostat 3 (S5) and 4 (S6) or relay R6.R6 starts if the temperatures at thermostat

Page 52 - Parallel relay

56Function descriptionsAdditional DHW heating function (cont.)Additional function in conjunction with additional Viessmann control unitsA DHW temperat

Page 53

57Function descriptionsThermostat function, ΔT control unit and time switchesThese functions are only available subject to the inputs and outputs not

Page 54 - Tank 2 ON

58Function descriptionsThermostat function, ΔT control unit and time switches (cont.)Setting values Display text/Factory default settingSetting range

Page 55 - Tank loading

59Parts list/appendixSpecificationRated voltage: 120VACRated frequency: 60 HzRated current: 10 APermissible ambient temperaturein operation:0 to +40

Page 56

6System designsSystem design 1 (cont.)A Solar panelB Solar-DiviconC Draw-off pointsD DHW circulationE DHW circulation output of boiler control unit or

Page 57

60Keyword indexKeyword indexAActual values (scan), 42Actuators, connecting, 29Additional DHW heating function, 47, 55Additional functions, 46BBypassw

Page 58

61Keyword indexKeyword indexTTank loading, 55Tank, max. temperature, 48, 49Tank temperature sensor, 31Temperature differentials, 48Temperature scannin

Page 59 - Specification

Viessmann Manufacturing Company Inc.750 McMurray RoadWaterloo, Ontario • N2V 2G5 • CanadaTel. (519) 885-6300 • Fax (519) 885-0887www.viessmann.ca • ma

Page 60 - Keyword index

7System designsSystem design 1 (cont.)Item DescriptionControl of DHW tank heating by solar energy1 Vitosolic 2002 Collector temperature sensor3 Tank t

Page 61

8System designsSystem design 2Dual-mode DHW heating with Vitocell-B 100 or Vitocell-B 300 DHW tanks – 2 collector arrays withdifferent orientationDHW

Page 62 - Quick Reference

9System designsSystem design 2 (cont.)A Solar panelB Solar-DiviconC Solar pump lineD Draw-off pointsE DHW circulationF DHW circulation output of boile

Commentaires sur ces manuels

Pas de commentaire