VIESMANN
VITODENS 200-W
Gas condensing boiler
17.0 to 105.0 kW
as a multi boiler system up to 840.0 kW
VITODENS 200-W Type WB2C
Wall mounted gas condensing boiler,
with modulating MatriX cylinder burner for natural gas and LPG
for open or balanced flue operation
5822 432 GB 5/2011
Technical guide
Vue de la page 0
1 2 3 4 5 6 ... 59 60

Résumé du contenu

Page 1 - VIESMANN

VIESMANNVITODENS 200-WGas condensing boiler17.0 to 105.0 kWas a multi boiler system up to 840.0 kWVITODENS 200-W Type WB2CWall mounted gas condensin

Page 2

Residual head of the circulation pump0 0,5 1 1,50100200300400500600Head in mbar0102030405060kPa2 2,5 3 3,5Pump rate in m³/hA BCAStage 1BStage 2CStage

Page 3 - (cont.)

KCable entry area at the backLWithout connection set (accessories)MWith connection set (accessories)NRecommended dimension (single boiler system)OReco

Page 4 - 1.1 Product description

Residual head of the circulation pump100Residual head in mbar00 1000Flow rate in l/h2006008001000300400500700900110012002000 3000 4000 50005000 6000AB

Page 5

2.1 Product descriptionInstallation accessories for the Vitodens 200-W, 45 and 60 kWHeating circuit connection set without circulation pumpPart no. 72

Page 6 - 1.2 Specification

Divicon heating circuit distributorConstruction and function Available with R ¾ , R 1 and R 1¼ connections. With heating circuit pump, check valve,

Page 7

142398ABCHV HR98120DG 1½abHV HRDivicon without mixer (wall mounting, shown without thermal insula-tion)HR Heating returnHV Heating flowAOverflow valve

Page 8

Determining the required internal diameterAΔT= 15KΔT= 20KΔT= 30KΔT= 5KΔT= 10KCBD2.52.5Mixer control characteristics2.00.10.20.51.01.55.0Flow rate in m

Page 9 - Pressure drop in mbar

ManifoldIncl. thermal insulationWall mounted with wall mounting bracket to be ordered separately.The connection between boiler and manifold must be ma

Page 10 - Vitodens 200-W

For 3 DiviconPart no. 7460 643 for Divicon R ¾ and R 1120HV HR HV HR HV HR120 120784HV HR135A180 180120G 1½Rp ¾AConnection option for expansion vessel

Page 11

Low loss headerPart no. 7460 649Flow rate max. 4.5 m3/hIncluding thermal insulation and integral sensor well.The connection between boiler and low los

Page 12

Index1. Vitodens 200-W 1.1 Product description ...

Page 13 - Installation accessories

with R ¾ = 1.0 m3/h with R 1 = 1.5 m3/h with R 1¼ = 2.5 m3/hExample:Flow rate ´ = 0.665 m3/hSelected:Divicon with mixer R ¾ and circulation pump Wilo

Page 14

CDivicon R 1¼ with mixerDDivicon R ¾, R 1 and R 1¼ without mixerHeating circuit pumps regulated by differential pressureAccording to the [German] Ener

Page 15

Operating mode: Variable differential pressureDA40010203001002003004000 0.5 1.0 1.5 2.0 2.5Pump rate in m³/hPressure drop/headmbarkPa50500606003.0 3.5

Page 16

Installation accessories for the Vitodens 200-W, 80 and 105 kWHeating circuit connection set with variable speed high efficiencycirculation pumpPart n

Page 17

Installation accessories for multi boiler systemsHydraulic cascadesSee page 28.Flue gas cascade (positive pressure)Comprising: Flue gas non-return de

Page 18

3.1 Product descriptionFor details regarding DHW cylinders, see the technical guide to theVitodens up to 35 kW, or separate datasheets.Design informat

Page 19

Electrical interlocks for extractors (extractor hoods, etc.) are notrequired with balanced flue operation.Vitodens 200-W from 60 kWInstall boilers fro

Page 20

Additional requirements when installing boilers with LPG opera-tion in rooms below ground levelAccording to TRF 1996 Vol. 2 – valid as of 1 September

Page 21

Pre-installation for installing the Vitodens 200-W directly onto a wall (single boiler)An installation template is supplied with the Vitodens 200-W fo

Page 22

Hydraulic cascade with low loss headercbahfgAB100E E882HV HR HV HRklHVHRedCRP 1DDShown without the thermal insulation suppliedASensor well for flow te

Page 23

5.4 Vitotronic accessories ... 45 Assignment to contr

Page 24

Boiler Number (2x2) 45 kW (2x2) 80 kW (2x3) 80 kW (2x4) 105 kW (2x2) 60 kW (2x2) 105 kW (2x3) 105 kW Heating circuit connection PN4/DN 80 100 100

Page 25 - DHW cylinder

HR Heating returnHV Heating flowBoiler Number 2x45 kW 2x80 kW 3x45 kW 3x80 kW 4x105 kW 6x 80 kW 8x 105 kW 2x60 kW 2x105 kW 3x60 kW 3x105 kW 6x 105 k

Page 26

Installation in series with flue gas cascade2001500F FA D678 6781750 a760CB580430cECHVHRbShown without the thermal insulation suppliedAFlue gas cascad

Page 27

Installation in block formation with a flue gas cascadea1750680 6801500bc200F FA DC BE760C580HVHRShown without the thermal insulation suppliedAFlue ga

Page 28

4.2 Condensate connectionRoute the condensate drain pipe with a constant fall.Route the condensate from the flue system (if equipped with a drain),tog

Page 29

The Vitodens can (if required) be supplied with a separate neutralisingsystem (accessory). Any condensate is piped to and treated in theneutralising s

Page 30

IP rating IP 44 Protection class FPermissible medium temperature +60 °CMax. head 45 kPaMax. capacity 450 l/hZero volt contact N/C, breaking capacity23

Page 31

Where water treatment is required, treat even the first fill of the heat-ing system prior to commissioning. This also applies to any subse-quent fil

Page 32

For installation schemes in conjunction with low loss headers, see therelevant sample application in the "System examples" document.Boiler c

Page 33

Programming unit: Easy operation through display with large font and depiction withgood contrast Removable programming unit; can be mounted as optio

Page 34 - 4.2 Condensate connection

1.1 Product descriptionAInox-Radial heat exchanger made from stainless steel – for highoperational reliability and a long service life. Large heating

Page 35

5.2 Vitotronic 200, type HO1B, for weather-compensated operationStructure and functionsModular structureThe control unit is integrated into the boiler

Page 36 - 4.3 Hydraulic connection

Adjusting the heating curves (slope and level)The Vitotronic 200 controls the boiler water temperature (= flow tem-perature of the heating circuit wit

Page 37

5.3 Vitotronic 300-K, type MW2B for multi boiler systemsCascade control unit for the Vitodens 200-W with Vitotronic 100Weather-compensated, digital ca

Page 38 - Structure and functions

DHW heating in a multi boiler systemAM MAVitotronic 300-KControl characteristics PI characteristics with three-point output Setting range for heatin

Page 39 - Control units

416680SpecificationIP rating IP 43 to EN 60529ensure through appropriatedesign/installationSensor typeViessmann NTC 10kΩ at25 °CPermissible ambient te

Page 40

Heating system with DHW cylinderOrder the circulation pump with check valve or the Vitotrans 222 pri-mary store system separately.5.4 Vitotronic acces

Page 41

Permissible ambient temperature – during operation 0 to +40 °C– during storage and transport -20 to +60 °CSet value range for standard andreduced

Page 42

Vitotrol 100, type UTDB-RFPart no. Z007 692Room temperature controller with integral wireless transmitter and onereceiver With digital time switch W

Page 43

NoteThe reduced room temperature (night temperature) is set at the con-trol unit. Party and economy mode can be enabled via keys. Only for heating

Page 44

Room temperature sensorPart no. 7438 537Separate room temperature sensor as supplement to the Vitotrol300A; to be used if the Vitotrol 300A cannot be

Page 45 - Vitotrol 100, type UTA

Installation with a self-supporting mounting frame in series andas a single blockComprising: Hydraulic cascade Connection set for every boiler with:

Page 46

Vitocom 100, type GSM Without SIM cardPart no. Z004594 With contract SIM card for the operation of the Vitocom 100 viamobile phonePart no. Z004615No

Page 47

Mixer extension kit for separate mixer motorPart no. 7301 062KM BUS subscriberFor the connection of a separate mixer motor.Components: Mixer PCB for

Page 48

SpecificationLead length 0.9 m, fully wiredIP rating IP 32 to EN 60529; ensurethrough appropriate designand installationSensor typeViessmann NTC, 10 k

Page 49 - Radio clock receiver

7213095200SpecificationLead length 4.2 m, fully wiredSetting range 30 to 80 °CSwitching differential max. 11 KBreaking capacity 6(1.5) A 250 V~Setting

Page 50

Cylinder temperature sensorFor connection inside the appliance.On-site extension of the power cable: 2-core lead, length up to 60 m with a cross-secti

Page 51

LON connecting cable for data exchange between control unitsVitotronic 300-K for the Vitotronic 200-HPart no. 7143 495Cable length 7 m, fully wired.Ex

Page 52

Internal extension H1Part no. 7179 057PCB for installation in the control unit.Using the extension allows the following functions to be achieved:Funct

Page 53

Extension EA1Part no. 7452 091Function extension inside the casing for wall mounting.Using the inputs and outputs allows up to 5 functions to be ach-i

Page 54

EnEV Energy Saving Ordinance1st BImSchV First regulation for the implementation of the German Immissions Act (regulation regarding small andmedium-siz

Page 55

AAccessories For control units...45Anti-corrosion agents...

Page 56

1.2 SpecificationGas boiler, series B and C, category II2N3PII2N3PII2N3PII2N3P Gas condensing boilerRated heating output range45 and 60 kW: Specif

Page 57 - 6.1 Regulations / Directives

60VIESMANNVITODENS 200-W5822 432 GBPrinted on environmentally friendly,chlorine-free bleached paperSubject to technical modifications.Viessmann Limite

Page 58

Gas boiler, series B and C, category II2N3PII2N3PII2N3PII2N3P Gas condensing boilerRated heating output range45 and 60 kW: Specification to EN 677

Page 59 - Keyword index

ORecommended dimension for a multi boiler systemPBalanced flue connection with bend (accessory)RCondensate drainSTop edge finished floorNoteLay all re

Page 60

Residual head of the circulation pumpABC00 200 400 600 800 1000Flow rate in l/h1200 1400 1600 1800 2000 2200 2400 2600Residual head in mbar0kPa1001020