VITOLA 200Start-up/Service Instructionsfor use by heating contractorVitola 200VB2 SeriesOil-/Gas-Fired BoilerHeating input 83 to 300 MBH24 to 88 kWRea
Start-up and Service105. Close combustion chamber door1. Push in combustion chamber insertas far as it will go. Handlemust be at bottom.The combustion
Start-up and Service118. Ensure proper operation of automatic fill valv e and expansion tank; also ensure proper system water pressureCheck fill press
Start-up and Service1211. Ensure that an adequate combustion air supply exists in the boiler roomEnsure fresh air intake of boiler room isopen. This o
Additional Information13Ordering Replacement Parts:Please provide boiler Model and SerialNumber from rating plate when orderingreplacement parts. Orde
Additional Information14Parts List012 Combustion chamber door013 Packing seal014 Combustion chamber doorrefractory032 Observation port cover033 Rope s
Additional Information15Notes5167 405 v2.2
Additional InformationViessmann Manufacturing Company Inc.750 McMurray RoadWaterloo, Ontario • N2V 2G5 • CanadaTel. (519) 885-6300 • Fax (519) 885-088
Safety, Installation and Warranty Requirements2Safety, Installation and Warranty RequirementsPlease ensure that this manual is read and understood bef
Safety, Installation and Warranty Requirements3Safety, Installation and Warranty Requirements (continued)Please ensure that this manual is read and un
Contents4PageSafetyImportant Regulatory and Installation Requirements 5...General InformationAbout these Service Instructions 6...
Safety5Important Regulatory and Installation RequirementsInstructing the system userThe installer of the system isresponsible to ensure the systemoper
General Information6About these Service InstructionsTake note of all symbols and notations intended to draw attention to potential hazards or importan
Start-up and Service7See Operating Instructions, Serv ice Instructions ofPower Burner and Boiler Control1. Ensure combustion and ventilation airopenin
Start-up and Service81. Shut down heating system1. Ensure main power supply toequipment, the heating sys tem, andall ext ernal controls has beendeacti
Start-up and Service93. Clean chimney, flue pipe and heat exchanger1. Check flue pipe condition, chimneyconnection, and chimney itself, bothinside and