VITOSOLIC 100Installation and serviceinstructionsfor heating engineersVitosolicĂ100Electronic temperature differential control unit for solar heating
10Installation and connectionsMains electrical connectionRegulationsCarry out the mains connection and all earthing measures (e.g. fault currentcircui
11Initial start-upStepsPage1. Probes or sensors correctly inserted into the sensor well?Ă 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.
12Initial start-upFurther details regarding individual steps (cont.)Adjusting system settingsAt the setting level (see below), the following parameter
13Initial start-upFurther details regarding individual steps (cont.)Relay test1. Select MM (manual mode) with"+" or "ć"; confirm w
14Service scansTemperaturesSubject to system version, using "+" or "ć", the following temperatures canbe scanned:Collector tempera
15TroubleshootingFault messagesSensor faults at S1 to S3 ( TC, TS, T3or TT) are displayed by the ON/OFFdisplay (flashes red) and through thefollowing
16TroubleshootingChecking sensors1. Disconnect the relevant sensorand measure the resistance.Temperaturein ºCResistancein W204050605465785976162. Comp
17TroubleshootingChanging the fuseA FuseOpen wiring chamber of control unit.Replacement fuse inside the pack.5862Ă490ĂGB230 V12 13 14 15 16 17 18 19 2
18System details/functionsSummarySetting(as deliveredcondition)SettingrangeExplanationSFĂćĂSpecial function*10 to 8 0: No functionDo not adjust if a s
19System details/functionsSummary (cont.)Setting(as deliveredcondition)SettingrangeExplanationSXĂćĂMaximum cylinder temperature2to90ĂºCPrevents the cy
2Safety instructionsSafety instructionsPlease follow these safety instructions closely to prevent accidents andmaterial losses.Safety regulationsInsta
20System details/functionsSummary (cont.)Setting(as deliveredcondition)SettingrangeExplanationFNĂćĂFunction0 to 3 0: Maximum cylinder temperature cont
21System details/functionsSpecial functionsMaximum cylinder limitSelect SFĂ=Ă1 at the setting level.The consumer connected to RĂ2 isstarted if the sel
22System details/functionsSpecial functions (cont.)A Connection extensionB VitosolicĂ100C Solar circuit pumpD Circulation pump for heating upthe pre-h
23System details/functionsSpecial functions (cont.)A Connection extensionF Cylinder temperaturesensorĂ(NTC)G Cylinder temperaturesensorĂ(PTC)L Vitotro
24System details/functionsSpecial functions (cont.)Additional function for DHW heatingOnly possible in conjunction with control unit with KM BUS (Vito
25System details/functionsMaximum cylinder temperature controlSelect FNĂ=Ă1 at the setting level.The solar circuit pump is switchedOFF if the set maxi
26System details/functionsReverse cooling functionOnly set in systems with flat collector panels.Select FNĂ=Ă2 at the setting level.The solar circuit
27Parts listParts listWhen ordering spare partsQuote the part no. and the item no.of the required part (as per this partslist).Obtain common parts fro
28AppendixSpecificationRated voltage: 230ĂV~Rated frequency: 50ĂHzRated current: 4ĂAPower consumption: 2ĂWSafety class: IIProtection: IPĂ20 toENĂ60529
29AppendixDeclaration of conformityWe, Viessmann Werke GmbHĂ&ĂCoĂKG, DĆ35107 Allendorf, declare as soleresponsible body, that the productVitosolic
3IndexIndexPageSystem designĂ4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30Keyword indexKeyword indexAActual values (scan),ă14Additional function for DHWheating,ă24AH (heat volume),ă14Applicability,ă32Automatic mode,ă20BCCi
31Keyword indexKeyword index (cont.)SSafety instructions,ă4Safety shutdown,ă4,ă19,ă25,ă26SensorsHĂChecking, ă16HĂConnection, ă22HĂInstallation,ă9Servi
Viessmann Werke GmbHĂ&ĂCoDĆ35107 AllendorfTel: +49 6452 70Ć0Fax: +49 6452 70Ć27Ă80www.viessmann.deViessmann LimitedHortonwood 30, TelfordShropshir
4System designSystem designDual mode DHW heating with VitocellĆBĂ100 or VitocellĆBĂ300DHW heating without solar energyThe upper indirect coil of the D
5System designSystem design (cont.)A Solar panelB SolarĆDiviconC Draw-off pointD DHW circulationE DHW circulation output of boiler control unit or on-
6System designSystem design (cont.)ItemDescription Number Part no.Control of DHW cylinder loading bysolar energy1 VitosolicĂ100 1 7170Ă9252 Collector
7Installation and connectionsControl unit installationInstallation locationNear the DHW cylinder, observing the electrical connections or theircable/l
8Installation and connectionsSolar circuit pumpInstallationThe "SolarĆDivicon" pumpstation includes thecirculation pump withconnecting cable
9Installation and connectionsSensorsCollector temperature sensorInstallationCollector installationinstructionsConnectionTo S1 (terminals 1 and 2).Exte