Viessmann Type B2HA Instructions d'exploitation

Naviguer en ligne ou télécharger Instructions d'exploitation pour Chauffe-eau et chaudières Viessmann Type B2HA. Viessmann Type B2HA Operating instructions Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 188
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Installation and service
instructions
for contractors
VIESMANN
Vitodens 200-W
Type B2HA, B2KA, 3.2 to 35 kW
Gas council no.
System boilers:
41-819-32; 41-819-33; 41-819-34; 41-819-35
Combi boilers:
47-819-28; 47-819-29; 47-819-30
For applicability, see the last page
VITODENS 200-W
5772 909 GB 11/2012
Please keep safe.
Vue de la page 0
1 2 3 4 5 6 ... 187 188

Résumé du contenu

Page 1 - VIESMANN

Installation and serviceinstructionsfor contractorsVIESMANNVitodens 200-WType B2HA, B2KA, 3.2 to 35 kWGas council no. System boilers:41-819-32; 41-81

Page 2 - Safety instructions

10Remove the toggle on the cold watershut-off valve (if installed) to preventanyone shutting it off manually.Shock arrestorIf draw-off points that cou

Page 3

100Weather-compensated control unit Constant temperature control unitCalling up the service levelService menu:1. Press OK and å simultaneously forappr

Page 4

101NoteDo not adjust menu item "Multi-boilersystem".The menu item turns a weather-compen-sated control unit into a constant tem-perature con

Page 5 - Service instructions

102Weather-compensated control unit Constant temperature control unitResetting operating dataSaved operating data (e.g. hours run) canbe reset to &quo

Page 6

103For an explanation of the relevant values in the individual lines and fields, seethe following table:Line (briefscan)Field 1 2 3 4 5 61: System sc

Page 7 - Intended use

104Line (briefscan)Field 1 2 3 4 5 69: Heating circuit A1/HC1Heating circuit M2/HC2Heating circuit M3/HC3Remotecontrol0: With-out1: Vitotrol200A/200

Page 8

105Brief scan for constant temperature control unitsService menu:1. Press OK and å simultaneously forapprox. 4 s."Ü" flashes on the display.

Page 9 - Cold water installation

106Brief scan Displayd Variablespeedpump1: Wilo2: Grundfos3: AscoliSoftwareversionVariablespeed pump0: No varia-ble speedpumpE1SoftwareversionSo

Page 10 - Preparing for installation

107Brief scan Display Solar control module SM1F5Stagnation time of the solar thermal system in hF6Night circulation, solar thermal system (number)F7M

Page 11 - Installation sequence

108Display ExplanationHtg circ pumpHC2ON Heating circuit pump output active (extension to heatingcircuit with mixer)Mixer HC2 Open "Mixer open&qu

Page 12 - Flue gas connection

109Display Explanation4 Diverter valve set to heating mode5 Diverter valve in central position (filling/draining)6 Diverter valve set to DHW mode10 In

Page 13 - Condensate connection

112x6.7.5.3.2x2.1.4.Installation sequenceFitting the boiler and making connections5772 909 GBInstallation

Page 14 - Gas connection

110Weather-compensated control unitIn the event of a fault, red fault indicatorA flashes. " " flashes on the displayand "Fault" is

Page 15

111Constant temperature control unitIn the event of a fault, red fault indicatorA flashes. The two-digit fault code and(subject to the type of fault)

Page 16 - Electrical connections

112Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause Measures10 X X Controls as ifthe outsidetemperaturewere 0 °CShort circuit,outsid

Page 17

113Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause Measures28 X X Regulates with-out flow tem-perature sen-sor (low lossheader)Lead

Page 18 - Outside temperature sensor !

114Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause Measures50 X X Onlytype B2HA:No DHW heat-ing by the boil-erShort circuitin the c

Page 19

115Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause Measures98 X X Control mode Lead break,temperaturesensor /Check sensor /on solar

Page 20

116Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresA7 X Control modeas per deliv-ered conditionProgrammingunit faultyReplac

Page 21

117Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresbC X Control modewithout remotecontrolCommunica-tion error, re-mote cont

Page 22

118Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresbE X Control modewithout remotecontrol Communica-tion error, re-mote con

Page 23 - Power supply

119Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresC5 X X Control mode,max. pumpspeedCommunica-tion error, var-iable speedi

Page 24 - Routing the connecting cables

12Fitting the connectionsA B C D E FAHeating flow BDHW (combi boilers)Cylinder flow (system boiler)CGas connectionDCold water (combi boilers)Cylinder

Page 25

120Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresCd X X Control mode Communica-tion errorVitocom 100,type GSM(KM BUS)Chec

Page 26 - Fitting the front panel

121Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresdC X Control modewithout roominfluenceShort circuit,room temper-ature se

Page 27

122Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresE1 X X Burner in a faultstateIonisationcurrent toohigh duringcalibration

Page 28

123Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresE7 X X Burner in a faultstateIonisationcurrent toolow duringcalibrationC

Page 29 - Filling the heating system

124Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresEA X X Burner in a faultstateIonisationcurrent out-side permissi-ble ran

Page 30

125Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresEd X X Burner in a faultstateInternal fault Replace controlunit.EE X X B

Page 31 - Venting the boiler

126Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresEF X X Burner in a faultstateFlame is lostimmediatelyafter it hasformed

Page 32 - Venting the heating system

127Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresF3 X X Burner in a faultstateFlame signalis alreadypresent atburner star

Page 33 - Filling the siphon with water

128Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresFd X X Burner in a faultstateFault, burnercontrol unit Check ignitionele

Page 34 - Checking the gas type

129Checking the outside temperature sensorX310010-20 -10 0 10 20 30Temperature in °C6820406080200Resistance in kΩSensor type: NTC 10 kΩ1. Pull plug &

Page 35

131. Pull the condensate hose far enoughout of the boiler that no unnecessarybends are created inside the boiler.Check the tightness of the siphoncon

Page 36

130Checking the boiler temperature sensor, cylinder temperaturesensor or low loss header flow temperature sensor%AX3TroubleshootingRepairs (cont.)5772

Page 37

13110110 30 50 70 90 110Temperature in °C0.40.60.8246820Resistance in kΩSensor type: NTC 10 kΩ1. Boiler water temperature sensorPull the leads from

Page 38

132Checking the outlet temperature sensor or comfort sensor(combi boilers only)BA10110 30 50 70 90 110Temperature in °C0.40.60.8246820Resistance in kΩ

Page 39 - Max. heating output setting

133Checking the plate heat exchangerBF G H KEDCAFHeating returnGCold waterHHeating flowKDHW 1. Shut off and drain the boiler on theheating water and

Page 40 - Burner removal

13410. DangerEscaping gas leads to a riskof explosion.Check all gas equipment fortightness.Checking the flue gas temperature sensorThe flue gas tempe

Page 41

135Fault "A3" during commissioningDuring commissioning, the control unitchecks whether the flue gas temperaturesensor is correctly positione

Page 42

136Checking the fuseF1A1. Switch off the power.2. Release the side closures and pivotthe control unit down.3. Remove cover A.4. Check fuse F1 (see

Page 43 - Cleaning the heating surfaces

137Checking the rotational direction ofthe mixer motorAfter being switched on, the boiler imple-ments a self-test. During this, the mixeris opened and

Page 44

138Checking flow temperature sensorPressure drop curve10110 30 50 70 90 110Temperature in °C0.40.60.8246820Resistance in kΩSensor type: NTC 10 kΩ1. Re

Page 45 - Fitting the burner

1394 8°Cs AHeating modeThe selected set boiler water tempera-ture will be maintained when a demandis being raised by the room thermostatand the heatin

Page 46

14A1. Seal gas shut-off valve A into thegas supply pipe.2. Carry out a tightness test.NoteOnly use suitable and approved leakdetection agents (EN 142

Page 47

140In the delivered condition, the set boilerwater temperature is 20 K above the setDHW temperature (adjustable via codingaddress "60" in gr

Page 48

141DHW heating with gas condensing combi boilerIf the flow switch detects that DHW isbeing drawn off (> 3 l/min), the burner,circulation pump and 3

Page 49

142Internal extension H1The internal extension is integrated intothe control unit casing. The followingalternative functions can be connectedto relay

Page 50

143Internal extension H2The internal extension is integrated intothe control unit casing. The followingalternative functions can be connectedto relay

Page 51

144Extension AM1A1 Circulation pumpA2 Circulation pumpfÖPower supplyfÖ APower supply for additionalaccessoriesaVGKM BUSFunction descriptionExternal ex

Page 52

145FunctionsOne of the following circulation pumpscan be connected to each of the connec-tions A1 and A2: Heating circuit pump for the heatingcircuit

Page 53

146Extension EA1A1 PCBF1 Fuse/MCBDE1 Digital input 1DE2 Digital input 2DE3 Digital input 30 – 10 V 0 – 10 V inputfÖPower supplyfÖ APower supply for ad

Page 54

147Digital data inputs DE1 to DE3The following functions can be connec-ted alternatively: External operating program change-over for each heating cir

Page 55

148Analogue input 0 – 10 VThe 0 – 10 V hook-up provides an addi-tional set boiler water temperature:0 – 1 V is taken as "no default for setboiler

Page 56 - +20 14 5

149You can select which direction the heat-ing program changeover takes in codingaddress "d5" in the "Heating circuit"group:Heatin

Page 57 - LON LON LON

15!Please noteElectronic assemblies can bedamaged by electrostatic dis-charge.Before beginning work, touchearthed objects, such as heatingor water pip

Page 58

150External blocking and fault message input CodeInput DE1 3A:4Input DE2 3b:4Input DE3 3C:4The effect on the internal circulationpump is selected in c

Page 59 - Instructing the system user

151Fill programIn the delivered condition, the divertervalve is set to its central position, ena-bling the system to be filled completely.After the co

Page 60 - Calling up coding level 1

152Temperature profile 2: (ZV parquet and flooring technology) code "F1:2"Flowtemperature °CDays50403020101 5 10 15 20 25 30Temperature prof

Page 61 - "General"/group 1

153Temperature profile 6: Code "F1:6"Flowtemperature °C1 5 10 15 20 25 30Days504030201060Temperature profile 7: Code "F1:15"Flowte

Page 62

154Example using the settings in the delivered conditionAB-20Outside temp. in °CBoiler water orflow temperature in °C8070605040300 -5 -10 -15510Set ro

Page 63

155Example using the settings in the delivered condition100203030405060600700800900Set boiler water or flowtemperature in °CTime in hABCDAStart of ope

Page 64 - "Boiler"/group 2

156The heating circuit allocation must beconfigured when commissioning theVitotrol.Heating circuit Vitotrol configuration200A/200 RF 300A/300 RFThe re

Page 65 - "Solar"/group 4

157Air ratio λ– CO2/O2 contentAir ratio λ O2 content(%)CO2 content(%) for natu-ral gas ECO2 content(%) for natu-ral gas LLCO2 content(%) for LPG P1.20

Page 66

158A1 Main PCBX... Electrical interface§Boiler water temperature sen-sor$Only type B2KA:Outlet temperature sensoraAIonisation electrodeaGFlue gas temp

Page 67

159dÖStepper motor for diverter valvefJTemperature limitergFIgnition unita-ÖFan motora-Ö AFan motor controlaVLOnly type B2KA:Flow switcha:ÖModulation

Page 68

16L N230V~230V~59640409620351001LN2 11452132 15 428145AAJumperInstallation sequenceElectrical connections5772 909 GB

Page 69

160A1 Main PCBA2 Power supply unitA3 OptolinkA4 Burner control unitA5 Programming unitA6 Coding cardDesignsConnection and wiring diagram – External co

Page 70

161A7 Connection adaptorA8 LON communication module(Vitotronic 200)A9 Internal extension H1 or H2(accessories)S1 ON/OFF switchS2 Reset buttonX... Elec

Page 71

162The following information is required: Serial no. (see type plate A) Assembly (from this parts list) Position number of the individual partwithin

Page 72

163BDF ECA0003AType plateBCasing assemblyCHeat cell assemblywith burnerDControl unit assemblyParts listsOverview of the assemblies5772 909 GBService

Page 73 - Calling up coding level 2

164EHydraulic assemblywith Aqua-plateFMiscellaneous assemblyCasing0001 Control unit support0002 Front panel0003 Viessmann logo0004 Fixing clip (2 pce)

Page 74

16500030004000400030002000600010005Heat cell0001 Gasket DN 600002 Boiler flue connection 60/1000003 Boiler flue connection plug0004 Flue gasketParts l

Page 75

1660005 Flue gas temperature sensor0006 Heat exchanger0007 Condensate hose0008 O-ring 35.4 x 3.6 (5 pce)0009 Locking clip, condensate hose0010 Siphon0

Page 76

16700150017000800090001000300150019001600140013001200090010 001100080010000700060017001800040003000500020001Parts lists Heat cell (cont.)5772 909 GBSe

Page 77

1680001 Burner gasket (wearing part)0002 Thermal insulation ring0003 Cylinder burner gauze assembly0004 Burner gauze assembly gasket0005 Ignition elec

Page 78

1690019001800040010000100040007001200130007001200130013000500060012001100140018000800160009000700170019001500040003001800020001Hydraulics type B2HA000

Page 79

17Connections at plug 230 V~fÖPower supplylH Power supply for accessories External demand/blocking Room temperature control unit(remove jumper A wh

Page 80

1700004 Clip Ø 8 (5 pce)0005 Thermal circuit breaker0006 Gasket set A 10 x 15 x 1.50007 Temperature sensor0008 Air vent valve G 3/80009 Heat exchanger

Page 81

171000800220024002000110016002000040006002300110016000600230004000300060004000700110008000500220013000900120024001400250021001100180019001600170016001

Page 82

172Aqua-plate type B2HA0001 Circulation pump motor0002 Linear stepper motor0003 Return unit0004 Adaptor for stepper motor0005 Screw 50 x 14 (5 pce)000

Page 83

1730010 Drain hose 10 x 1.5 x 15000011 O-ring 20.6 x 2.6 (set)0012 Diaphragm grommet0013 Plug-in connector retainer (set)0014 Pressure gauge0015 Heati

Page 84

174002000250008002200240011001600200004000600230011001600060023000400030006000400070011000800050022001300090012002400140021001100180019001600170016001

Page 85

175Aqua-plate type B2KA0001 Circulation pump motor0002 Linear stepper motor0003 Return unit0004 Adaptor for stepper motor0005 Screw 50 x 14 (5 pce)000

Page 86

1760001 Control unit0002 Control unit casing back panel0003 Coding card0004 Fuse 6.3 A (slow) (10 pce)0005 Fuse holder0006 Programming unit for consta

Page 87

1770009000600020020001500050009001900110010002100030008001800170014000400050015001500010007001200220013Miscellaneous0001 Spray paint, Vitowhite0002 To

Page 88

178000400050006000200030001Parts lists Miscellaneous (cont.)5772 909 GB

Page 89

179Settings and actual values Set value Commis-sioningMainte-nance/Service Date Signature Static pressure mbarkPa≤ 57.5≤ 5.75

Page 90

18Outside temperature sensor !For fitting the wireless outside tempera-ture sensor (wireless accessory):Wireless base station installationand service

Page 91

180Rated voltage 230 VRated frequency 50 HzRated current 6 ASafety category IIP rating IP X 4 D toEN 60529Permissible ambient temperature During oper

Page 92

181Combi boiler (type B2KA)Rated heating outputrange at TV/TR 50/30 °C kW 5.2 - 26(8.8 - 26)*25.2 - 30(8.8 - 30)*25.2 - 35(8.8 - 35)*2at TV/TR 8

Page 93

182We, Viessmann Werke GmbH&Co KG, D-35107 Allendorf, declare as sole respon-sible body that the product Vitodens 200-W, type B2HA and B2KA, compl

Page 94

183AAcknowledging a fault display...110Actuator test...107Assembly...16

Page 95

184LLanguage selection...30LON...57 Fault monitoring...

Page 96

1855772 909 GB

Page 97

1865772 909 GB

Page 98

1875772 909 GB

Page 99

188ApplicabilitySerial No.:7454869 7454870 7454871 74548727454873 7454874Viessmann LimitedHortonwood 30, TelfordShropshire, TF1 7YP, GBTelephone: +44

Page 100 - Service level

19Plug lHExtension EA1AlHN?1LAFloating contact (when connecting,remove jumper across L and 1) B[{SDE[{DDE[{ADEAAFloating contactBExtension EA1Codes &

Page 101 - Operating data

2Please follow these safety instructions closely to prevent accidents and mate-rial losses.Safety instructions explainedDangerThis symbol warns agains

Page 102 - Brief scan

20L?NL?NfÖSPaBJ230 V~Ö[{{]0-10Vf-]AU0-10 V++-0 – 1 V≙ No default set boiler watertemperature1 V≙ Set value 10 °C10 V≙ Set value 100 °CExternal blocki

Page 103

21Plug lHExtension EA1AlHN?1LAFloating contact (when connecting,remove jumper across L and 1) B[{SDE[{DDE[{ADEAAFloating contactBExtension EA1Codes &

Page 104

22Power supply for accessories at plug lH (230 V~)Where the boiler is installed in a wetarea, the power supply connection foraccessories must not be m

Page 105

23A buffer relay must be fitted if the currentflowing to the connected working parts(e.g. circulation pumps) is higher thanthe safety level of the rel

Page 106

24Routing the connecting cables!Please noteIf power cables touch hot compo-nents they will be damaged. When routing and securingcables/leads on site,

Page 107

255.4.2.6.2x3.1.Insert programming unit (packed sepa-rately) into the control unit support.NoteThe programming unit can also be inser-ted into a wall

Page 108 - 5772 909 GB

262x1.2.3.NoteFit the safety guard and ensure that thelocking screws are tightened beforeoperating.Installation sequenceFitting the front panel5772 90

Page 109

27For further information regarding the individual steps, see the page indicatedCommissioning stepsInspection stepsMaintenance steps Page•1. Checking

Page 110 - Fault display

28Commissioning stepsInspection stepsMaintenance steps Page• •20. Checking and adjusting the ignition and ionisationelectrodes...

Page 111

29Filling the heating systemFill water!Please noteUnsuitable fill water increasesthe level of deposits and corro-sion and may lead to boiler dam-age.

Page 112 - Fault codes

3If you smell flue gasDangerFlue gas can lead to life-threat-ening poisoning. Shut down the heating system. Ventilate the installation site. Close

Page 113

30NoteIf the control unit has not beenswitched on prior to filling the system,then the servomotor of the divertervalve will still be in its central po

Page 114

31Note on the automatic flue gas temperature sensor testWeather-compensated control unit Constant temperature control unitAs soon as the time and date

Page 115

321. Close the shut-off valves on the heat-ing water side. If required, remove thesafety guard.2. Push the drain hose (supplied insidethe appliance)

Page 116

33Activating the venting functionWeather-compensated control unit Constant temperature control unitService menu1. Press OK and å simultaneously forapp

Page 117

34NoteNever twist the supply hose duringassembly. Route the drain hose with-out any bends and with a constantfall.Designating heating circuits - only

Page 118

35Gas type conversion (only for operation with LPG)12A1. Set adjusting screw A on the gastrain to "2".2. Turn on the ON/OFF switch 8.3. Se

Page 119

36A1. Close the gas shut-off valve.2. Undo screw A in test nipple "IN" onthe gas train but do not remove it, andconnect the pressure gauge.

Page 120

37Supply pressure (flow pressure) ActionFor natural gas For LPGBelow 17.4 mbar Below 25 mbar Do not start the boiler. Notify your gassupply utility or

Page 121

38 Yes Ionisation currentbuilds Symbol ANoFault EE Check the ionisa-tion electrode ad-justment and thegas line for air-locks. Yes

Page 122

39Max. heating output settingThe maximum output for heating oper-ation can be limited. The limit is set viathe modulation range. The max. adjust-able

Page 123

4Auxiliary components, spare andwearing parts!Please noteSpare and wearing parts thathave not been tested togetherwith the system can compromiseits fu

Page 124

40Burner removalFGDE4xCBA1. Switch OFF the power supply and theON/OFF switch at the control unit.2. Close the gas shut-off valve and safe-guard agai

Page 125

41Checking the burner gasket and burner gauze assemblyCheck burner gasket A and burnergauze assembly E for possible damageand replace if required.AC2x

Page 126

424. Insert new burner gauze assemblyE with new gasket F and secure.!Please noteFasten screws tightly enoughto ensure the components arenot being dam

Page 127

43Cleaning the heating surfaces!Please noteThere should be no scratches orother damage on the heatexchanger surface that comesinto contact with hot ga

Page 128

44AB1. Check at the siphon that the conden-sate can drain freely.2. Remove retaining clip A and siphonB.3. Clean siphon B.4. Fill siphon B with water

Page 129 - Resistance in kΩ

45Fitting the burnerFGDE4xCBA1. Fit the burner and tighten screws Gdiagonally.!Please noteFasten screws tightly enoughto ensure the components arenot

Page 130 - (cont.)

46Checking the flow limiter (only for combi boilers)CBA1. Switch OFF the control unit, shut offthe cold water line and drain the DHWside of the boile

Page 131

473. Top up with water until the chargepressure of the cooled system is atleast 1.0 bar, and is 0.1 to 0.2 barhigher than the pre-charge pressureof t

Page 132 - (combi boilers only)

48A1. Connect a flue gas analyser at fluegas port A on the boiler flue con-nection.2. Open the gas shut-off valve, start theboiler and create a heat

Page 133

49Matching the control unit to the heating systemThe control unit must be adjusted subjectto the system equipment level. To do this, select the relev

Page 134

5Installation instructionsPreparing for installationIntended use...

Page 135

50Function/system components CodeAdjust GroupOperation with LPG 82:1 "General"/1System with DHW circulation pump: DHW circulation pump c

Page 136 - Checking the fuse

519Heating circuit pump M2qPExtension kit for one heating circuitwith mixer M2Function/system components CodeAdjust GroupOperation with LPG 82:1 &quo

Page 137

525Heating circuit without mixer A1(heating circuit 1)6Heating circuit with mixer M2(heating circuit 2)7Temperature limiter to restrict themaximum tem

Page 138

53System version 4One heating circuit without mixer, one heating circuit with mixer M2 (withextension kit), one heating circuit with mixer M3 (with ex

Page 139 - Heating mode

54Function/system components CodeAdjust GroupOperation with LPG 82:1 "General"System only with two heating circuits with mixer withextensio

Page 140

550.2Outside temperature in °CBoiler water orFlow temperature in °CSlope2.42.62.83.03.23.4908070605040300 -5 -10 -15 -205102.02.2Set room temperature

Page 141 - Boosting DHW heating

56DHeating circuit pump "OFF" EHeating circuit pump "ON"Changing the standard set room temper-atureOperating instructionsReduced s

Page 142 - Internal extension H1

57Connecting the control unit to the LON system - only for weather-compensated control unitsThe LON communication module(accessories) must be plugged

Page 143 - Internal extension H2

58Boiler control unit Vitotronic 200-H Vitotronic 200-H VitocomViessmann systemnumber,Code "98:1".Viessmann systemnumber,Code "98:1&quo

Page 144 - Extension AM1

59Calling up and resetting the service displayThe red fault indicator flashes when thelimits set in coding addresses "21" and"23"

Page 145

6TroubleshootingFault display... 110Fault codes.

Page 146 - Extension EA1

60Calling up coding level 1 On weather-compensated controlunits, codes are displayed as plaintext. Codes that have not been assigneddue to the heati

Page 147

61Weather-compensated control unit Constant temperature control unitResetting all codes to their delivered conditionSelect "Standard setting"

Page 148 - Control functions

62Valueaddress00: ...SystemversionDescription7 4 One heating circuit with mixer M2 (heating circuit 2) and oneheating circuit with mixer M3 (heating c

Page 149 - External blocking

63Coding in the delivered condition Possible changeSubscriber no.77:1 LON subscriber number(only for weather-com-pensated control units)77:2to77:99LON

Page 150 - Venting program

64Select "Boiler" for weather-compensa-ted control units (see page 60).Select "2" for constant temperature con-trol units (see pag

Page 151 - Screed drying

65CodingCoding in the delivered condition Possible changeSet DHW temperature reheating suppression67:40 For solar DHW heating:Set DHW temperature40 °C

Page 152

66Coding in the delivered condition Possible changeCylinder maximum temperature08:60 Set DHW temperature(maximum cylinder tem-perature) 60 °C.08:10to0

Page 153

67Select "Heating circuit ..." for weather-compensated control units (seepage 60).Select "5" for constant temperature con-trol uni

Page 154 - Reducing the heat-up time

68Coding in the delivered condition Possible changeExtended economy function adjusted outside temperatureA6:36 Extended economy con-trol disabled (onl

Page 155

69Coding in the delivered condition Possible changeWeather-compensated/room temperature hook-upb0:0 With remote control:Heating mode/reducedmode: weat

Page 156

7The appliance is only intended to beinstalled and operated in sealed unven-ted heating systems that comply withEN 12828, with due attention paid to t

Page 157

70Coding in the delivered condition Possible changeMax. flow temperature heating circuitC6:74 Electronic maximum flowtemperature limit 74 °C(only for

Page 158

71Coding in the delivered condition Possible changeMin. pump speedE7:30 Minimum speed of thevariable speed heatingcircuit pump: 30 % of themax. speed

Page 159

72Coding in the delivered condition Possible changeStart temperature raisingF8:–5 Temperature limit for ter-minating reduced mode–5 °C, see example on

Page 160

73Calling up coding level 2 All codes are accessible in codinglevel 2. Codes that have not been assigneddue to the heating system equipmentlevel or

Page 161

74Weather-compensated control unit Constant temperature control unitResetting all codes to their delivered conditionSelect "Standard setting"

Page 162 - Ordering individual parts

75Valueaddress00: ...SystemversionDescription7 4 One heating circuit with mixer M2 (heating circuit 2) and oneheating circuit with mixer M3 (heating c

Page 163 - Overview of the assemblies

76Coding in the delivered condition Possible change34:0 Function output A2 at ex-tension AM1: DHW circu-lation pump34:1 Function output A2: Heat-ing c

Page 164

77Coding in the delivered condition Possible change3b:0 Function input DE2 at ex-tension EA1: Not as-signed3b:1 Function input DE2: Heat-ing program -

Page 165 - Heat cell

78Coding in the delivered condition Possible change3C:3 Function input DE3: Exter-nal blocking.Internal circulation pumpfunction: Coding address3E3C:4

Page 166 - Heat cell

79Coding in the delivered condition Possible change51:0 System with low lossheader: Internal circulation pumpalways starts when thereis a heat demand5

Page 167

8!Please noteTo prevent equipment damage,connect all pipework free of loadand torque stress.3604507301925H850100 21550aA B C D EF KGAHeating flow Rp¾B

Page 168

80Coding in the delivered condition Possible change6E:51to6E:100Display correction +0.1 Kto +5 K76:0 Without LON communi-cation module (only forweathe

Page 169 - Hydraulics type B2HA

81Coding in the delivered condition Possible change81:2 Use of the radio clock re-ceiver (automatic recogni-tion)81:3 With LON communicationmodule: Th

Page 170 - Hydraulics type B2HA

82Coding in the delivered condition Possible change98:1 Viessmann system num-ber (in conjunction withmonitoring several sys-tems via Vitocom 300)98:1t

Page 171

83CodingCoding in the delivered condition Possible change01:1 Do not adjust (only forconstant temperaturecontrol units) 04:1 Minimum burner pausetim

Page 172 - Hydraulics type B2KA

84Coding in the delivered condition Possible change30:1 Internal variable speedcirculation pump (auto-matic adjustment)30:0 Internal circulation pumpw

Page 173 - Hydraulics type B2KA

85Coding in the delivered condition Possible change5b:0 DHW cylinder directlyconnected to the boiler 5b:1 DHW cylinder connecteddownstream of the low

Page 174

86Coding in the delivered condition Possible change67:40 For solar DHW heating:Set DHW temperature40 °C. Reheating is sup-pressed above the selec-ted

Page 175 - Aqua-plate type B2KA

87NoteThe solar group is only displayed if asolar control module, type SM1, is con-nected.CodingCoding in the delivered condition Possible change00:8

Page 176 - Control unit

88Coding in the delivered condition Possible change08:60 Set DHW temperature(maximum cylinder tem-perature) 60 °C.08:10to08:90Set DHW temperature ad-j

Page 177 - Miscellaneous

89Coding in the delivered condition Possible change Target temperaturecontrol switched on(code "10:1"):Temperature at whichthe solar heated

Page 178 - Miscellaneous

9Rated heating outputkWDim. amm3.2 - 19.0 1366.5 - 26.0 1588.8 - 35.0 158NoteThis boiler (IP rating: IP X4D) isapproved for installation in wet roomsi

Page 179 - Commissioning/service reports

90Coding in the delivered condition Possible change22:8 Start temperature differ-ential with central heatingbackup (code "20:4" mustbe selec

Page 180 - Specification

91Coding in the delivered condition Possible changeAfter the selected cyclicalheating time for the DHWcylinder without priorityhas expired, the rise i

Page 181

92Parameter Heating circuit pump Address A3:... "ON" "OFF"–9 –10 °C –8 °C–8 –9 °C –7 °C–7 –8 °C –-6 °C–6 –7 °C –5 °C–5 –6 °C –4 °C

Page 182 - Declaration of conformity

93Parameter addressA5:...With heating circuit pump logic function: Heating cir-cuit pump "OFF"1 AT > RTset + 5 K2 AT > RTset + 4 K3 AT

Page 183 - Keyword index

94Coding in the delivered condition Possible changeA8:1 Heating circuit with mixercreates a demand for theinternal circulation pump(only for weather-c

Page 184

95Coding in the delivered condition Possible changeb2:64b5:0 With remote control: Noroom temperature-de-pendent heating circuitpump logic function (on

Page 185

96Coding in the delivered condition Possible changed5:0 The external heating pro-gram changeoverswitches the heating pro-gram to "Constant opera-

Page 186

97Coding in the delivered condition Possible changeE2:50 With remote control: Nodisplay correction for theactual room temperature(only for weather-com

Page 187

98Coding in the delivered condition Possible changeF1:0 Screed drying disabled(only for weather-com-pensated control units).F1:1toF1:6Screed drying ad

Page 188 - Applicability

99Coding in the delivered condition Possible changeObserve the setting ofcoding address "A3". (on-ly for weather-compensa-ted control units)