VITOTRONIC 100, GC1
VITOCONTROL-S, VD2/CT3/CM2
Installation and
Service Instructions
for use by heating contractor
Vitotronic 100, Model GC1
Digital boiler control unit
Vitocontrol-S, VD2 / VD2A / CT3, CM2 Model 300-K MW1
Outdoor-reset logic digital cascade control
Certified as a component part
of Viessmann boilers only
Please file in Service Binder
5351 340 v1.4 05/2012
Vue de la page 0
1 2 3 4 5 6 ... 195 196

Résumé du contenu

Page 1 - Service Instructions

VITOTRONIC 100, GC1VITOCONTROL-S, VD2/CT3/CM2Installation andService Instructionsfor use by heating contractorVitotronic 100, Model GC1Digital boiler

Page 2

10Heating system designsSystem version 2Vitorond 200, VD2A Boiler with Vitotronic 100, GC1B Vitocontrol-S, VD2/CT3/CM2C DHW tankD Mixing valve circuit

Page 3

Slope2.22.01.81.61.41.21.00.80.60.40.23.43.23.02.82.62.4110/230100/21270/15860/14050/12240/10430/8680/17690/1941050541032-523-20-4-1014-155Supply temp

Page 4

101Initial start-upFurther step-by-step instructions(continued)Changing slope and shift(for every heating circuit separately)1. Call up slope with ,ad

Page 5 - Product information

102Initial start-upFurther step-by-step instructions(continued)Adjusting the normal room temperature(for every heating circuit separately)Normal room

Page 6

103Service scanning – Vitotronic 100, GC1Service level summaryFunction Entry Exit PageRelay test Press the 9 and “OK”buttons simultaneously forapprox.

Page 7

104Service scanning – Vitotronic 100, GC1Temperatures, boiler coding card and quick scans1. Press 9 and rw simultaneouslyfor approx. two seconds.2. Se

Page 8 - Summary of system versions

105Service scanning – Vitotronic 100, GC1Temperatures, boiler coding card and quick scans(continued)ScansF8 F8 8 8 8 80000N/ALON participant number So

Page 9 - System Version 1

106Service scanning – Vitotronic 100, GC1Scanning operating conditions1. Press .2. Select the required operatingcondition scan with or .3. Press .The

Page 10 - System version 2

107Service scanning – Vitotronic 100, GC1Scanning and resetting maintenance displaysAfter limits have been reached, which were set up via coding addre

Page 11 - IMPORTANT

108Service scans – Vitocontrol-S, VD2/CT3/CM2Service level summaryFunction Entry Exit PageAdjusting displaycontrastPress the “OK” and “+”buttons simul

Page 12 - System version 3

109Service scans – Vitocontrol-S, VD2/CT3/CM2Temperatures and quick scans1. Press 9 and rw simultaneouslyfor approx. 2 seconds.2. Select the required

Page 13

11Heating system designsSystem version 2(continued)Codings must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boil

Page 14

110Service scans – Vitocontrol-S, VD2/CT3/CM2Temperatures and quick scans(continued)8N/ASoftware versionPlug-in adaptorfor ext. safetyequipmentSoftwar

Page 15 - System version 4

111Service scans – Vitocontrol-S, VD2/CT3/CM2Scanning operating conditions1. Press .2. Select the required scanwith or .3. Press .The following values

Page 16

112Service scans – Vitocontrol-S, VD2/CT3/CM2Scanning and resetting maintenance displayVitocontrol-S, VD2/CT3/CM2 displays a maintenance message if:V

Page 17 - System version 5

113Troubleshooting – Vitotronic 100, GC1Faults displayed at the programming unit1 Consecutive fault number38 Fault codeU Fault symbolRed fault lamp A

Page 18

114Troubleshooting – Vitotronic 100, GC1Faults displayed at the programming unit(continued)FaultcodeSystem characteristicsCause Remedy0000ffffControl

Page 19 - System version 6

115Troubleshooting – Vitotronic 100, GC1Faults displayed at the programming unit(continued)FaultcodeSystem characteristicsCause Remedybbbb8888Control

Page 20

116Troubleshooting – Vitotronic 100, GC1Viewing fault codes from the fault memory (error history)1. Press rw and simultaneouslyfor approx. 2 seconds.2

Page 21

117Troubleshooting – Vitocontrol-S, VD2/CT3/CM2Faults displayed at the programming unit(continued)Fault display in plain textExt. faultOutdoor tempe

Page 22 - System version 7

118Troubleshooting – Vitocontrol-S, VD2/CT3/CM2Faults displayed at the programming unit(continued)FaultcodeSystem characteristicsCause Remedy4444ccccO

Page 23

119Troubleshooting – Vitocontrol-S, VD2/CT3/CM2Faults displayed at the programming unit(continued)FaultcodeSystem characteristicsCause Remedy99992222C

Page 24

12Heating system designsSystem version 3Common supply pump and low pressure distribution manifoldVitorond 200, VD2A Boiler with Vitotronic 100, GC1B V

Page 25 - System version 8

120Troubleshooting – Vitocontrol-S, VD2/CT3/CM2Faults displayed at the programming unit(continued)FaultcodeSystem characteristicsCause RemedybbbbccccC

Page 26

121Troubleshooting – Vitocontrol-S, VD2/CT3/CM2Faults displayed at the programming unit(continued)FaultcodeSystem characteristicsCause RemedyddddaaaaC

Page 27

122Troubleshooting – Vitocontrol-S, VD2/CT3/CM2Viewing fault codes from the fault memory (error history)1. Press rw and simultaneouslyfor approx. 2 se

Page 28 - System version 9

123Function description – Vitotronic 100Boiler temperature controlBrief descriptionThe boiler water temperature isregulated by controlling a two stage

Page 29

124Function description – Vitocontrol-S, VD2/CT3/CM2Cascade control unitBrief descriptionThe supply temperature is regulated bystarting or stopping th

Page 30

125Function description – Vitocontrol-S, VD2/CT3/CM2Cascade control(continued)Control sequenceStand-alone (Autonomous) type of control sequenceParalle

Page 31 - System version 10

126Function description – Vitocontrol-S, VD2/CT3/CM2Cascade control(continued)Sequential type of control sequence(coding 3b: 4)With the sequential typ

Page 32

127Function description – Vitocontrol-S, VD2/CT3/CM2Cascade control(continued)Net calorific strategy 1Conventional boilers are preferablyoperated at t

Page 33

128Function description – Vitocontrol-S, VD2/CT3/CM2Cascade control(continued)Control strategy exampleTwo boiler system with modulating burner:Boiler

Page 34

129Function description – Vitocontrol-S, VD2/CT3/CM2Cascade control(continued)Net calorific strategy 2 (coding 3C: 2)Start-up Switching OFFBoiler sequ

Page 35 - Installation

13Heating system designsSystem version 3(continued)Coding must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boile

Page 36

130Function description – Vitocontrol-S, VD2/CT3/CM2Heating circuit controlBrief descriptionThe control unit provides controlcircuits for one high tem

Page 37

131Function description – Vitocontrol-S, VD2/CT3/CM2Heating circuit control(continued)Domestic hot water temperatureWith priority control:The set sup

Page 38

132Function description – Vitocontrol-S, VD2/CT3/CM2Heating circuit control(continued)Supply temperature controlDifferential temperature:The different

Page 39

133Function description – Vitocontrol-S, VD2/CT3/CM2DHW tank temperature controlBrief descriptionThe DHW tank control logic is aset-point control. It

Page 40

134Function description – Vitocontrol-S, VD2/CT3/CM2DHW tank temperature control(continued)Control sequencePump delayThe DHW pump continuous operatio

Page 41 - Sensor connection

135Function description – Vitocontrol-S, VD2/CT3/CM2Components from the parts listLine voltage motherboardThe main Printed Circuit Boardcomprises:Rel

Page 42

136Components – Vitotronic 100, GC1Components from the parts listLON communication modulePlug in the LON communication module into the control unit.Th

Page 43

137Components – Vitotronic 100, GC1Components from the parts list(continued)Boiler water temperature sensorThe sensor measures the boiler watertempera

Page 44

138Components – Vitotronic 100, GC1Components from the parts list(continued)Strap-on temperature sensor and immersion temperature sensorFor measuring

Page 45

139Components – Vitotronic 100Flue gas temperature sensor (for VD2/VD2A/CT3 only)The sensor measures the flue gastemperature and monitors the selected

Page 46

14Heating system designsSystem version 3(continued)Possible applicationsIf the distribution manifold is located ina remote location (> 20 m / 65 ft

Page 47 - (VD2/VD2A/CT3 only)

140Components – Vitocontrol-S, VD2/CT3/CM2Components from the parts listLine voltage motherboardThe main printed circuit boardcomprises:Relays and ou

Page 48 - (CM2 only)

141Components – Vitocontrol-S, VD2/CT3/CM2Components from the parts list(continued)LON communication moduleThe communication interruption will be disp

Page 49

142Components – Vitocontrol-S, VD2/CT3/CM2Components from the parts list(continued)Strap-on temperature sensor and immersion temperature sensorTo meas

Page 50

143Components – Vitocontrol-S, VD2/CT3/CM2Components from the parts list(continued)Outdoor temperature sensorConnectionSee page 77.Check sensor1. Remo

Page 51

144Components – Vitocontrol-S, VD2/CT3/CM2Mixing valve circuit extension kitMixing valve motor, Part No. 7133 390A Plug in the mixing valve motor| Mix

Page 52

KRHVKVHRHRKVHVKRHVKVHRKRHVKVHRKVHVHRHRHVKRKVHVHRKRKVHVKVHRKR145Components – Vitocontrol-S, VD2/CT3/CM2Installation examplesMixing valve insert convers

Page 53

146Components – Vitocontrol-S, VD2/CT3/CM2Remote controlVitotrol 200, Part No. 7133 378(with integral room temperature sensor for room temperature fee

Page 54

147Components – Vitocontrol-S, VD2/CT3/CM2Remote control(continued)D Printed circuit board DIP switches(rear of the top casing)Remote controlaffectsDI

Page 55

148Components – Vitocontrol-S, VD2/CT3/CM2Remote control(continued)Vitotrol 300, Part No. 7134 452(with integral room temperature sensor for room temp

Page 56

149Components – Vitocontrol-S, VD2/CT3/CM2Remote control(continued)D Printed circuit board DIP switches(rear of the top casing)Remote controlaffectsDI

Page 57

15Heating system designsSystem version 4Controlling the return temperature with a 3-way mixing valveVitorond 200, VD2A Boiler with Vitotronic 100, GC1

Page 58

150Components – Vitocontrol-S, VD2/CT3/CM2Remote control(continued)Connecting several remote control unitsWhen connecting several remote controls to t

Page 59

151Components – Vitocontrol-S, VD2/CT3/CM2Remote control(continued)Version 2A To control unitB Terminal box (on site)C Vitotrol 1D Vitotrol 2E Vitotro

Page 60

152Components – Vitocontrol-S, VD2/CT3/CM2Room temperature sensor,Part No. 7133 379The room temperature sensor measures the actual room temperature, i

Page 61 - Making the LON connection

153Components – Vitocontrol-S, VD2/CT3/CM2Input Module 0 to 10 V,Part No. 7134 561From software version 7 of Vitocontrol-S, VD2/CT3/CM2, the Input Mod

Page 62

154Coding – Vitotronic 100, GC1Coding 1Calling up coding 11. Press 9 and w simultaneously forapprox. two seconds, until the firstarrow appears in the

Page 63

155Coding – Vitotronic 100, GC1Coding 1(continued)Coding in the factory setting Possible changeBoiler/burner06: 87 Maximum boiler water temperature li

Page 64

156Coding – Vitotronic 100, GC1Coding 2Calling up coding 21. Press w and rw simultaneouslyfor approx. 2 seconds, until the firsttwo arrows appear in t

Page 65

157Coding – Vitotronic 100, GC1Coding 2(continued)Coding in the factory setting Possible changeBurner (mod.) (see page 97)05: 70 Burner curve 05: 0 Li

Page 66

158Coding – Vitotronic 100, GC1Coding 2(continued)Coding in the factory setting Possible changeBoiler0C: 5Isolation valve modulating independently of

Page 67

159Coding – Vitotronic 100, GC1Coding 2(continued)Coding in the factory setting Possible changeBurner (two stage/mod.)16:*1Burner offset in ˚C / ˚F:Te

Page 68

16Heating system designsSystem version 4(continued)Coding must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boile

Page 69

160Coding – Vitotronic 100, GC1Coding 2(continued)Coding in the factory setting Possible changeBoiler/burner24: 0 No maintenance indication 24: 1 Main

Page 70

161Coding – Vitotronic 100, GC1Coding 2(continued)Coding in the factory setting Possible changeGeneral (continued)2C: 5Maximum time delay of isolation

Page 71

162Coding – Vitotronic 100, GC1Coding 2(continued)Coding in the factory setting Possible changeGeneral4E: 0 Connection on plug gS:Isolation valve or t

Page 72

163Coding – Vitotronic 100Burner switching differentialFor adjustment, see coding 04 on page 156.Switching differential 4˚C / 7˚F (coding 04: 0)Heat d

Page 73

164Coding – Vitocontrol-S, VD2/CT3/CM2Coding 1Calling up coding 11. Press 9 and w simultaneously forapprox. 2 seconds.2. Select the required coding ad

Page 74 - (continued)

165Coding – Vitocontrol-S, VD2/CT3/CM2Coding 1(continued)Coding in the factory setting Possible changeMulti-boiler control unit36: 0 Electronic minimu

Page 75 - Mounting of the control unit

166Coding – Vitocontrol-S, VD2/CT3/CM2Coding 1(continued)Coding in factory setting Possible changeGeneral (continued)77: 5 LON participant number 77:

Page 76

167Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2The summary from page 168 lists all possible coding addresses.The coding addresses are grouped inaccorda

Page 77

168Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Overall summaryCoding in the factory setting Possible changeSystem design00: 1 See page 164Mu

Page 78

169Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in the factory setting Possible changeMulti-boiler control (continued)3d: 1 Output bal

Page 79

17Heating system designsSystem version 5Controlling the return temperature with a low loss header and a three-way mixing valveVitorond 200, VD2A Boile

Page 80

170Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeMulti-boiler control (continued)48: 35 Only for sequ

Page 81

171Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in the factory setting Possible changeDHW56: 0 Setting range for DHW temperature:10 to

Page 82 - Connection of the pumps

172Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeDHW (continued)67: 40 With Vitosolic:3rdDHWset-point

Page 83

173Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeGeneral (continued)7b: 1 Transmitting time via LON B

Page 84

174Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeGeneral (continued)92:184 Do not adjustAddress will

Page 85

175Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeGeneral (continued)99: 0 Connection to terminals 2 a

Page 86

176Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeGeneral (continued)9b: 70Set minimum supply temperat

Page 87 - Power supply

177Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeSystem circuit/mixing valve circuit (continued)A4: 0

Page 88

178Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeMixing valve circuitAA: 2With output reduction throu

Page 89 - Opening the control unit

179Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeSystems/mixing valve circuit (continued)b7: 0*1With

Page 90

18Heating system designsSystem version 5(continued)Coding must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boile

Page 91

180Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeSystems/mixing valve circuit (continued)C8:31*1With

Page 92

181Coding – Vitocontrol-S, VD2/CT3/CM2Coding 2(continued)Coding in factory setting Possible changeSystems/mixing valve circuit (continued)F8: -5 With

Page 93

70/15860/14050/12240/10430/8680/17690/1941050541032-523-20-4-1014-155Supply temperature in ºC / ºFOutdoor temperature in ºC / ºFSet room temperature i

Page 94 - F01 : 01

183Coding – Vitocontrol-S, VD2/CT3/CM2Slab curing function diagramCoding, see page 180.Temperature-time profile 1 (coding F1: 1)(See back of manual fo

Page 95

184Connection and wiring diagrams – Vitotronic 100, GC1SummaryA2 Low voltage motherboardA3 Line voltage motherboardA6 Programming unitA7 Optolink prin

Page 96

185Connection and wiring diagrams – Vitotronic 100, GC1Low voltage motherboard§ Boiler temperature sensor% No functionaG Flue gas temperature sensoraJ

Page 97

186Connection and wiring diagrams – Vitotronic 100, GC1Line voltage motherboardsÖ Control outputsA DHW pumpsL Shunt or boiler circuit pumpfÖ Power sup

Page 98

187Connection and wiring diagrams – Vitotronic 100. GC1Line voltage motherboard(continued)5351 340 v1.4A11A3floatingONON

Page 99

188Connection and wiring diagrams – Vitocontrol-S, VD2/CT3/CM2SummaryA1 Mixing valve extension boardA2 Low voltage motherboardA3 Line voltage motherbo

Page 100 - 5351 340 v1.4

189Connection and wiring diagrams – Vitocontrol-S, VD2/CT3/CM2Low voltage motherboard! Outdoor temperature sensor? Common supply temperaturesensor§ No

Page 101

19Heating system designsSystem version 6Heating circuit and one low temperature heating circuitVitocrossal 300, CT3A Boiler with Vitotronic 100, GC1B

Page 102

190Connection and wiring diagrams – Vitocontrol-S, VD2/CT3/CM2Line voltage motherboardsÖ Heating circuit pumpsA DHW pump (accessory)sK DHW recirculati

Page 103 - Service level summary

191Connection and wiring diagrams – Vitocontrol-S, VD2/CT3/CM2Mixing valve extension Printed Circuit Board? Supply temperature sensorsÖ Heating circui

Page 104

192AppendixSpecification – Vitotronic 100, GC1Rated voltage: 120VACRated frequency: 60 HzRated current: 2 × 6 A~Powerconsumption: 5 WSafety class: IPr

Page 105 - F8 F8 8 8 8 8

193AppendixParts ListVVVVIIIITTTTOOOOTTTTRRRROOOONNNNIIIICCCC 333300000000----KKKKMW1 SeriesOrder No.Vitocontrol-SMW1W (shown to right)Custom Control

Page 106 - Scanning operating conditions

194AppendixParts List(continued)Other Parts (not illustrated)060 Accessory pack (plugs)080 Installation / Service InstructionsVitotronic 100/333081 Op

Page 107

1955351 340 v1.4

Page 108

Viessmann Manufacturing Company Inc.750 McMurray RoadWaterloo, Ontario • N2V 2G5 • CanadaTel. (519) 885-6300 • Fax (519) 885-0887www.viessmann.ca • in

Page 109 - Temperatures and quick scans

General information2Safety, Installation and Warranty requirementsPlease ensure that this manual is read and understood before commencing installation

Page 110

20Heating system designsSystem version 6(continued)Codings must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boil

Page 111

21Heating system designsSystem version 6(continued)Possible applicationsVitocrossal 300 is operated via aViessmann boiler control unit withoutdoor res

Page 112 - MMaintenance

22Heating system designsSystem version 7Heating circuit and one low temperature heating circuit plus Vitorond with shunt pumpVitocrossal 300, CT3Vitor

Page 113

23Heating system designsSystem version 7(continued)Coding must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boile

Page 114

24Heating system designsSystem version 7(continued)Possible applicationsThe Vitocrossal 300, CT3 (lead boiler) and the Vitorond 200, VD2 (lag boiler)

Page 115

25Heating system designsSystem version 8Three-way mixing valve, several heating circuits and one low temperature heating circuitVitocrossal 300, CT3Vi

Page 116 - Outdoor temp. sensor

26Heating system designsSystem version 8(continued)Coding must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boile

Page 117

27Heating system designsSystem version 8(continued)Vitocontrol-S, VD2/CT3/CM2Required coding00: 3,00: 4,00: 7,or00: 8Without system circuit A1*135: 13

Page 118

28Heating system designsSystem version 9Heating circuit and one low temperature heating circuitVitocrossal 200, CM2A Boiler with Vitotronic 100, GC1B

Page 119

29Heating system designsSystem version 9(continued)Codings must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boil

Page 120

3ContentsIndexPageProduct information 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 121 - Participant

30Heating system designsSystem version 9(continued)Possible applicationsVitocrossal 200 is operated via aViessmann boiler control unit withoutdoor res

Page 122 - Error history

31Heating system designsSystem version 10Heating circuit and one low temperature heating circuit plus Vitorond with shunt pumpVitocrossal 200, CM2Vito

Page 123 - Control sequence

32Heating system designsSystem version 10(continued)Coding must be set on every Vitotronic 100, GC1.Vitotronic 100, GC1Required coding01: 2 Multi-boil

Page 124 - Set supply temperature

33Heating system designsSystem version 10(continued)Possible applicationsThe Vitocrossal 200, CM2 (lead boiler) and the Vitorond 200, VD2 (lag boiler)

Page 125 - Cascade control

34Installation – Vitotronic 100, GC1Summary of electrical connectionsLow voltage connections (motherboard)§ Boiler temperature sensor% No functionaG F

Page 126

Installation35Overview of Electrical Connections (VD2/VD2A/CT3 only) (continued)5351 340 v1.4[29][20] A1

Page 127

Installation36Overview of Electrical Connections (CM2 only) (continued)5351 340 v1.4

Page 128

37Installation – Vitotronic 100, GC1Inserting cables and applying strain reliefRun the cables from the connection enclosure into the control unit.Appl

Page 129 - Boiler sequence

38Installation – Vitotronic 100, GC1Inserting the boiler coding cardOnly use the boiler coding card included with the boiler.Boiler Coding card Part n

Page 130 - Heating circuit control

39Installation – Vitotronic 100, GC1Setting of the fixed high limit(if required)Settings on the control unitThe setting for the fixed high limit andth

Page 131

4ContentsIndex(continued)Service scanning – Vitotronic 100Service level summary 103. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 132

Installation40Setting of the Adjustable High Limit (if required)The adjustable high limit is suppliedwith a factory setting of 95°C / 203°FAdjustment

Page 133 - DHW tank temperature control

41Installation – Vitotronic 100, GC1Sensor connectionATemperature sensor T2BTemperature sensor T1CBoiler temperature sensorDFlue gas temperature senso

Page 134

42Installation – Vitotronic 100, GC1Connection of the boiler temperature sensorThe sensor measures the boiler watertemperature of the boiler.The boile

Page 135

43Installation – Vitotronic 100, GC1Connection of the return temperature sensorStrap-on temperature sensor and immersion temperature sensorFor measuri

Page 136

44Installation – Vitotronic 100, GC1Connection of the flue gas temperature sensor (VD2/VD2A/CT3 only)The sensor measures the flue gastemperature and m

Page 137 - Boiler temperature in

Installation45Connection of the Pumps (VD2/VD2A/CT3 only)Available pump connectionssÖ Switched contactTerminals 5 - L, - G , - NsL Shunt pump, boiler

Page 138 - Return temperature in °C / °F

Installation46Connection of the Pumps (CM2 only)Available pump connectionssÖ Switched contactTerminals 7 - L, - G , - NsL Shunt pump, boiler circuit p

Page 139

Installation47Connection of Boiler Return Mixing Valve or Isolation/Modulating Valve actuator(VD2/VD2A/CT3 only)1 120V or 24V Valve Adaptor2 DIN rail

Page 140

Installation48Connection of Boiler Return Mixing Valve or Isolation/Modulating Valve actuator(CM2 only)1 120V or 24V Valve Adaptor2 Junction box3 120V

Page 141 - DHW tank temperature sensor

Installation49Making Space for Accessory Adaptors on the DIN Rail (CM2 only)1. Push up on the bottom front ofthe DIN rail clamp to remove andset aside

Page 142

5ContentsIndex(continued)Coding – Vitocontrol-S, VD2/CT3/CM2Resetting codings to the factory setting 163. . . . . . . . . . . . . . . . . . . . . . .

Page 143 - Resistance in

Installation50Vitotronic 100, GC1 with 30% LTP Package (VD2/VD2A only)5351 340 v1.4VD2/VD2A1 - 17B Sensor (strap-on)

Page 144 - Mixing valve motor

51Installation – Vitotronic 100, GC1Connection of external controlsABoiler disableConnect dry contact at terminals “1”and “2” of the plug aVD.Contact

Page 145 - Installation examples

Installation52Connection of Low Water Cut-off Device (VD2/VD2A/CT3 only)aBH Power supply for accessories.aBÖ Connection for externalequipment.1. Remov

Page 146 - Vitotrol 200

Installation53Connection of Low Water Cut-off Device (CM2 only)1. Remove jumper between terminals21 and 22.2. Make connection as shown indiagram.5351

Page 147

Installation54Connection of Combustion Air Device (VD2/VD2A/CT3 only)Connection of the Combustion AirDevice Adaptor1. Disconnect power to control andb

Page 148 - Vitotrol 300

Installation55Connection of Combustion Air Device (CM2 only)Connection of the Combustion AirDevice Adaptor1. Disconnect power to control andburners.2.

Page 149

56Installation – Vitotronic 100, GC1Connection of combustion air devices(continued)Connection of the combustion airdamperSee damper manual for correct

Page 150

57Installation – Vitotronic 100, GC1Connection of single combustion air devices on mulitple boiler systemIf a single combustion air device isrequired

Page 151

58Installation – Vitotronic 100, GC1Connection of single combustion air devices on mulitple boiler systemConnection of the combustion airblowerA Commo

Page 152 - Room temperature sensor

59Installation – Vitotronic 100, GC1Connection of single combustion air damperConnection of the combustion airdamperA Common Combustion Air DeviceInte

Page 153 - Input Module 0 to 10 V

Important Precautions6SafetyTake note of all symbols and notations intended to draw attention to potential hazards or important product information.Th

Page 154 - Calling up coding 1

60Installation – Vitotronic 100, GC1Connection of the compiled failure alarm(VD2/VD2A/CT3 only)Connection of the compiledfailure alarm(CM2 0nly)Rated

Page 155

61Installation – Vitotronic 100, GC1Plugging in the LON communication modulePlug in the LON communication modulein accordance with the illustration in

Page 156 - Overall summary

62Installation – Vitotronic 100, GC1Burner connection, burner control wiring (VD2/VD2A/CT3 only)For burners with plug-in connectionThe burner cables a

Page 157

63Installation – Vitotronic 100, GC1Burner connection, burner control wiring(VD2/VD2A/CT3 only) (continued)Write the terminal numbers ormarkings on th

Page 158

Installation64Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only) (continued)Burner motor power supply connection(continued)For burners with

Page 159

Installation65Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only) (continued)Burner motor power supply connection(continued)For burners with

Page 160

Installation66Power Supply Connection, Boiler Control (VD2/VD2A/CT3 only)LegendL: LineN: NeutralG: GroundA Power supply 120 VAC, 1 PH .Provide disconn

Page 161

Installation67Burner Connection, Burner Control Wiring (CM2 only)For burners with plug-in connectionThe burner cables are included in thestandard deli

Page 162

68Installation – Vitotronic 100, GC1Installing the control unit front (VD2/VD2A/CT3 only)1. Position the front part of the housingand clip hinges to c

Page 163 - Burner switching differential

69Installation – Vitotronic 100, GC1Opening the control unit (VD2/VD2A/CT3 only)1. Remove the cover of the connectionenclosure.2. Unscrew the screws f

Page 164

Important Precautions / General Information7Important regulatory and installation requirementsPower supplyInstall power supply in accordance withthe r

Page 165

Installation70Control and Junction Box Installation Instructions (for CM2 only)1. Route cables and capillaries fromcontrol through the opening in thec

Page 166

Installation71Mounting the Front Part of the Control Unit (CM2 only)1. Position the front part of the housingand clip hinges to counter-parts onmain h

Page 167

Installation72Opening the Control Unit (CM2 only)1. Remove the control cosmeticcover .2. Unscrew the screws from thefront housing.3. Swing up the fron

Page 168

73Installation – Vitocontrol-S, VD2/CT3/CM2Summary of electrical connectionsMixing valve extension circuit board?M2/M3 Supply temperature sensorsÖM2/M

Page 169

74Installation – Vitocontrol-S, VD2/CT3/CM2Summary of electrical connections(continued)5351 340 v1.4Vitocontrol-S VD2/CT3/CM2, 300-K MW1

Page 170

75Installation – Vitocontrol-S, VD2/CT3/CM2Mounting of the control unit1.Fasten metal backplate ontomounting surface with fourfasteners.2.Position mid

Page 171

76Installation – Vitocontrol-S, VD2/CT3/CM2Inserting cables and applying strain reliefRun the cables from the connection enclosure into the control un

Page 172

77Installation – Vitocontrol-S, VD2/CT3/CM2Sensor connectionAOutdoor temperature sensor(not polarity sensitive)BReturn temperature sensor T2Installati

Page 173

78Installation – Vitocontrol-S, VD2/CT3/CM2Sensor connection(continued)Outdoor temperature sensorThe outdoor temperature sensor should be mounted 2 to

Page 174

79Installation – Vitocontrol-S, VD2/CT3/CM2Sensor connection(continued)Strap-on temperature sensor and immersion temperature sensorFor measuring the s

Page 175

8General informationSummary of system versionsBoiler Characteristics Page1 Vitorond 200,VD2AWith Therm-Control and 3-way mixing valve 92 Vitorond 200,

Page 176

80Installation – Vitocontrol-S, VD2/CT3/CM2Sensor connection(continued)Strap-on temperature sensor and immersion temperature sensorFor measuring the r

Page 177

81Installation – Vitocontrol-S, VD2/CT3/CM2Sensor connection(continued)DHW tank temperature sensorThe sensor measures the domestic hotwater tank tempe

Page 178

82Installation – Vitocontrol-S, VD2/CT3/CM2Connection of the pumpsAvailable pump connectionssA DHW pump for heating up thedomestic hot water tank -Ter

Page 179

83Installation – Vitocontrol-S, VD2/CT3/CM2Connection of modulating valve actuators1 120V or 24V valve adaptor2 DIN rail in connection enclosure3 aBH

Page 180

84Installation – Vitocontrol-S, VD2/CT3/CM2Connection of external contactsA External heating programchangeover or mixing valve “open”Contact closed:Th

Page 181

85Installation – Vitocontrol-S, VD2/CT3/CM2Connection of the compiled failure alarmRated voltage: 120 VAC 60 HzRated current: max. 2 FLARecommended co

Page 182

86Installation – Vitocontrol-S, VD2/CT3/CM2Making the LON connectionThe Viessmann LON system is designed for the Line BUS topology with end of line re

Page 183 - Slab curing function diagram

87Installation – Vitocontrol-S, VD2/CT3/CM2Making the LON connection(continued)Connection withViessmann LON cable,On-site cable for extensions

Page 184

88Installation – Vitocontrol-S, VD2/CT3/CM2Installing the control unit front1. Position the front part of the housingand clip hinges to counter-parts

Page 185 - Low voltage motherboard

89Installation – Vitocontrol-S, VD2/CT3/CM2Opening the control unit1. Remove the cover of the connectionenclosure.2. Unscrew the screws from the front

Page 186 - Line voltage motherboard

9Heating system designsSystem Version 1Vitorond 200, VD2ALON LON connection (available connections with terminator)A Heating circuit with mixing valve

Page 187

90Initial start-upSteps.Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 188

91Initial start-upFurther step-by-step instructionsChecking the heating circuit allocation (Vitocontrol-S, VD2/CT3/CM2)Check whether the label for he

Page 189

92Initial start-upFurther step-by-step instructions(continued)Connecting control units to the LON systemThe LON communication module must be plugged i

Page 190

93Initial start-upFurther step-by-step instructions(continued)Example of a multi-boiler systemMulti boiler systems withcascade control via LON-BUSSet

Page 191 - Applicability

94Initial start-upFurther step-by-step instructions(continued)Carrying out a participant check (Vitocontrol-S, VD2/CT3/CM2)The communication with the

Page 192 - 5351 340 v1.45351 340 v1.4

95Initial start-upFurther step-by-step instructions(continued)Matching coding addresses to respective system versionVitotronic 100In coding 1, set the

Page 193 - Parts List

96Initial start-upFurther step-by-step instructions(continued)Matching the control unit to a two stage burner (Vitotronic 100, GC1)1. Start up the bur

Page 194

97Initial start-upFurther step-by-step instructions(continued)Matching the control unit to a modulating burner (Vitotronic 100, GC1)Please note:The bu

Page 195

98Initial start-upFurther step-by-step instructions(continued)Checking outputs (actuators) and sensorsVitotronic 100Relay test1. Press 9 and simul

Page 196 - Quick Reference

99Initial start-upFurther step-by-step instructions(continued)Vitocontrol-S, VD2/CT3/CM2Relay test1. Press 9 and simultaneously forapprox. two second