Please file in Service Binder5285 873 - 02 12/2014Installation Instructionsfor use by heating contractorVITOCROSSAL 300Vitocrossal 300 CT3 SeriesGas-
Vitocrossal 300, CT3 Series Installation 5285 873 - 0210Set-upMinimum Clearances (continued)LegendV Vent pipe connectionSH Female connection R½ i
115285 873 - 02Vitocrossal 300, CT3 Series InstallationSet-upBoiler DimensionsDimensionsBoiler ModelCT3-1722283748577289ain. (mm) 28c(715)28c(715)28c
Vitocrossal 300, CT3 Series Installation 5285 873 - 0212Set-upBoiler Handling, Positioning and AdjustmentsPlease observe the minimum clearances starti
135285 873 - 02Vitocrossal 300, CT3 Series InstallationAssemblyAssembly When Supplied in Sections1. Release the turnbuckles and screws M 12 on the bo
Vitocrossal 300, CT3 Series Installation 5285 873 - 0214Boiler ConnectionsWater Side Connections1. The existing heating system must be properly flush
155285 873 - 02Vitocrossal 300, CT3 Series InstallationBoiler ConnectionsHydrostatic Test ProcedureAll Vitocrossal boilers are factory tested (hydrost
Vitocrossal 300, CT3 Series Installation 5285 873 - 0216Boiler Piping in Heating/Cooling ApplicationBoiler ConnectionsThe boiler, when used in connect
175285 873 - 02Vitocrossal 300, CT3 Series InstallationBoiler ConnectionsInitial System FillThe pressure relief valve must be attached to the top tapp
Vitocrossal 300, CT3 Series Installation 5285 873 - 0218Condensate ConnectionBoiler Connections1. Locate the neutralization unit either behind or nex
195285 873 - 02Vitocrossal 300, CT3 Series InstallationBoiler Connections/AssemblyCondensate DisposalAll condensate disposal piping from boiler and fr
Vitocrossal 300, CT3 Series Installation 5285 873 - 022 Safety, Installation and Warranty RequirementsSafetyPlease ensure that these instructions are
Vitocrossal 300, CT3 Series Installation 5285 873 - 0220Insulation InstallationAssembly1. Remove combustion chamber door. Remove all hexagon bolts an
215285 873 - 02Vitocrossal 300, CT3 Series InstallationAssemblyInsulation Installation (continued)10. Attach front panel with three screws M 8 x 10 to
Vitocrossal 300, CT3 Series Installation 5285 873 - 0222Preparing the Control Unit InstallationAssembly1. Attach the bottom of the mounting panel A w
235285 873 - 02Vitocrossal 300, CT3 Series InstallationPreparing the Control Unit Installation (continued)AssemblyCAUTIONMaximum allowable operating t
Vitocrossal 300, CT3 Series Installation 5285 873 - 02246. Attach the bottom of the finned panels with self- tapping screws B 3.9×9.5.7. Attach th
255285 873 - 02Vitocrossal 300, CT3 Series InstallationAssemblyInsulation Installation (continued)Top panel installation1. Fit the back panel onto th
Vitocrossal 300, CT3 Series Installation 5285 873 - 0226AssemblyObservation Port InstallationBurner InstallationThe combustion chamber is equipped wit
275285 873 - 02Vitocrossal 300, CT3 Series InstallationAssemblyBurner Blast Tube Insulation1. Mount burner plate A on combustion chamber door B (if n
Vitocrossal 300, CT3 Series Installation 5285 873 - 0228AssemblyBurner SettingsFlexmaster Canada Limited452 Attwell DriveEtobicoke, ON M9W 5C3Tel.: (4
295285 873 - 02Vitocrossal 300, CT3 Series InstallationStart-UpRecommended Flow RatesBoiler model CT3- 17 22 28 37 46 57 72 8920° F ∆t GPM 61 81 103 1
35285 873 - 02Vitocrossal 300, CT3 Series InstallationSafety Safety, Installation and Warranty Requirements (continued)WARNINGInhaling of fiberglass w
Vitocrossal 300, CT3 Series Installation 5285 873 - 0230AppendixBoiler ModelCT3-1722283748577289InputMBH (kW)638(187)846(248)1071 (314)1389 (407)1726
315285 873 - 02Vitocrossal 300, CT3 Series InstallationAppendixTechnical Data (continued)*3 Boiler has two return connections - the heating return w
Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper.5285
4 PageTable of Contents5285 873 - 02Vitocrossal 300, CT3 Series InstallationSafety, Installation and Warranty Requirements ...2Product docu
Table of Contents5 Page5285 873 - 02Vitocrossal 300, CT3 Series InstallationAssemblyStart-upAppendixInsulation Installation ...
Vitocrossal 300, CT3 Series Installation 5285 873 - 026Safety Important Regulatory and Safety RequirementsFor installations on the Commonwealth of Mas
75285 873 - 02Vitocrossal 300, CT3 Series InstallationSafety Important Regulatory and Safety Requirements (continued)Working on the equipmentThe inst
Vitocrossal 300, CT3 Series Installation 5285 873 - 028General InformationWARNINGExposing the boiler to pressures and temperatures in excess of those
95285 873 - 02Vitocrossal 300, CT3 Series Installation Mechanical RoomThe Vitocrossal 300, CT3 boiler should be located in a heated indoor space. The