Viessmann Vitodens 222-F Instructions d'exploitation

Naviguer en ligne ou télécharger Instructions d'exploitation pour Chauffe-eau et chaudières Viessmann Vitodens 222-F. Viessmann Vitodens 222-F Operating instructions Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 164
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Installation and service
instructions
for contractors
VIESMANN
Vitodens 222-F
Type FS2B
Compact gas condensing boiler
4.8 to 35 kW natural gas and LPG version
For applicability, see the last page
VITODENS 222-F
5457 552 GB 2/2010
Please keep safe.
Vue de la page 0
1 2 3 4 5 6 ... 163 164

Résumé du contenu

Page 1 - VIESMANN

Installation and serviceinstructionsfor contractorsVIESMANNVitodens 222-FType FS2BCompact gas condensing boiler4.8 to 35 kW natural gas and LPG versio

Page 2 - Safety instructions

10Safety assembly to DIN 1988ASafety assembly to DIN 1988(accessory to connection sets forunfinished walls)BSafety valveCVisible blow-off line outletD

Page 3

100Display ExplanationStart valve Heating Diverter valve set to heating modeStart valve centre Diverter valve in central position (filling/draining)St

Page 4 - Service instructions

101Display Explanation19Contacts P - S at plug aBJ for extension EA1 closed20 Output A1 at extension AM1 enabled21 Output A2 at extension AM1 enabledD

Page 5

102Weather-compensated control unitIf there is a fault, the red fault indicatorA flashes. " " flashes on the displayand "Fault" is

Page 6 - Product information

103Constant temperature control unitIf there is a fault, the red fault indicatorA flashes. The two-digit fault code and(subject to the type of fault)

Page 7

104Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause Measures10 X X Regulates as ifthe outsidetemperaturewere 0 °CShort circuit,outsi

Page 8

105Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause Measures48 X Mixer closes Lead break,flow tempera-ture sensor,heating circuit2 (

Page 9

106Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresA9 X The burneroperates at itslower output if aheating circuitwith mixer

Page 10 - Preparing for installation

107Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause Measuresbb X Mixer regulatesto a flow tem-perature of20 °CCommunica-tion error,e

Page 11 - Installing the boiler

108Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresC4 X X Control mode Communica-tion error,Open ThermextensionCheck OpenTh

Page 12

109Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresCE X X Control mode Communica-tion error, ext.extensionCheck electricalc

Page 13 - Gas connection

11Assembling the boiler2.6.7.5.1.4.2x3.Installation sequenceInstalling the boiler5457 552 GBInstallation

Page 14 - Flue gas connection

110Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause Measuresdd X Control modewithout roominfluenceLead break,room temper-ature senso

Page 15 - Electrical connections

111Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresEb X X Burner in a faultstateHeat draw-offrepeatedlytoo low duringcalibr

Page 16

112Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresEF X X Burner in a faultstateFlame is lostafter flamehas built.Check the

Page 17

113Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresF8 X X Burner in a faultstateThe fuel valvecloses toolateCheck the gastr

Page 18 - Routing the connecting cables

114Dis-playedfaultcodeConst. Weath.-comp.System char-acteristicsCause MeasuresFE X X Burner blockedor in a faultstateBoiler codingcard or mainPCB faul

Page 19

115Putting control unit in maintenance positionIf required for commissioning and serv-icing, the control unit can be put in a dif-ferent position.1.2.

Page 20 - Installation sequence

116Draining the boiler on the heating water side1. Close the shut-off valves on the heat-ing water side.2. Route hose at drain valve A into asuitable

Page 21

1172. Test the resistance of the outsidetemperature sensor across terminals"X3.1" and "X3.2" on the disconnec-ted plug and compar

Page 22

118Checking the boiler temperature sensor, cylinder temperaturesensor or flow temperature sensor of the low loss headerX35TroubleshootingRepairs (cont

Page 23 - Filling the heating system

1191. Boiler water temperature sensorPull the leads from boiler watertemperature sensor A and checkthe resistance. Cylinder temperature sensorPull

Page 24

12Connections on the heating water and the DHW sideShown with connection sets for finished walls (accessories)AHeating flow R ¾BDHW R ½CDHW circulatio

Page 25

120Checking the outlet temperature sensor1. Pull the leads from outlet temperaturesensor A.10110 30 50 70 90 110Temperature in °C0.40.60.8246820Resis

Page 26 - Venting the heating system

121Checking the flue gas temperature sensorThe flue gas temperature sensor locks out the boiler when the permissible flue gastemperature is exceeded.

Page 27 - Filling the siphon with water

122Checking the plate heat exchangerNoteDrain the boiler on its heating water and DHW side.During removal, small amounts of water may trickle out and

Page 28 - Checking the gas type

1236. Check the connections on the heat-ing water and DHW side for contam-ination and scaling; if required,replace the plate heat exchanger.7. Insta

Page 29

124Checking the fuseF11. Switch OFF the power.2. Release the side closures and pivotthe control unit down.3. Remove cover A.4. Check fuse F1 (see c

Page 30

125Checking the rotational direction ofthe mixer motorAfter being switched ON, the boilerimplements a self-test. During this, themixer is opened and c

Page 31

1264 8°Cs AHeating modeThe selected set boiler water tempera-ture will be maintained when a demandis being raised by the room thermostatand the heatin

Page 32 - Setting the maximum output

127Boosting when DHW is drawn offWhen DHW is drawn off, cold waterenters at the bottom of the primary cyl-inder.The heating circuit pump is switched O

Page 33

128Heating modeThe control unit determines a set boilerwater temperature subject to outsidetemperature or room temperature (if aroom temperature-depen

Page 34 - Burner removal

129The DHW is controlled to the specifiedtemperature via the cylinder temperaturesensor.The primary cylinder continues to beheated up after the draw o

Page 35 - CADE 3xFB

13Gas connectionNotes regarding operation with LPG.We recommend the installation of anexternal safety solenoid valve wheninstalling the boiler in room

Page 36

130Internal extension H1The internal extension H1 is integratedinto the control unit casing. The cylinderprimary pump is connected to relay out-put sK

Page 37

131Internal extension H2 (accessories)The internal extension H2 is integratedinto the control unit casing instead of theinternal extension H1. The cyl

Page 38 - Checking the anode connection

132Extension AM1A1 Circulation pumpA2 Circulation pumpfÖPower supply [terminals]fÖAPower supply terminal for addi-tional accessoriesaVGKM BUSFunction

Page 39

133FunctionsOne of the following circulation pumpscan be connected to each of the termi-nals A1 and A2: Heating circuit pump for the heatingcircuit w

Page 40

134Extension EA1DE1 Digital input 1DE2 Digital input 2DE3 Digital input 30 - 10 V 0 - 10 V inputfÖPower supply [terminals]fÖAPower supply terminal for

Page 41

135Digital data inputs DE1 to DE3The following functions can be connec-ted alternatively: External heating program changeoverfor each heating circuit

Page 42 - Cleaning the primary store

136Function assignmentSelect the function of output aBJ viacode 36 at the boiler control unit.Control functionsExternal heating program changeoverThe

Page 43

137Heating program changeover CodeNo heating program changeover F2:0Duration of the heating program changeover 1 to 12 hours F2:1 toF2:12 The heating

Page 44

138External demand CodeInput DE1 3A:2Input DE2 3b:2Input DE3 3C:2The effect on the internal circulationpump is selected with code 3F.The effect on the

Page 45

139When the screed drying function is acti-vated, the heating circuit pump of themixer circuit is switched ON and the flowtemperature will be held in

Page 46

14!Please noteExcessive test pressure maydamage the boiler and the gasvalve.Max. test pressure 150 mbar.Where higher pressure isrequired for tightness

Page 47

140Temperature profile 3: Code "F1:3"Flowtemperature °CDays50403020101 5 10 15 20 25 30Temperature profile 4: Code "F1:4"Flowtempe

Page 48

141Temperature profile 6: Code "F1:6"Flowtemperature °C1 5 10 15 20 25 30Days504030201060Temperature profile 7: Code "F1:15"Flowte

Page 49

142Example using the settings in the delivered conditionAB-20Outside temp. in °CBoiler water orflow temperature in °C8070605040300 -5 -10 -15510Set ro

Page 50

143Example using the settings in the delivered condition100203030405060600700800900Set boiler water or flowtemperature in °CTime in hABCDAStart of ope

Page 51

144The heating circuit assignment must beconfigured when commissioning theVitotrol 200A or Vitotrol 300A.Heating circuit ConfigurationVitotrol 200A Vi

Page 52

145Air factor λ – CO2/O2 contentAir factor λ O2 content (%) CO2 content (%) for nat-ural gas HCO2 content (%) forLPG P1.24 4.4 9.2 10.91.27 4.9 9.0 10

Page 53

146A1 Main PCBX... Electrical interfaces§Boiler water temperature sensor$Outlet temperature sensoraAIonisation electrodeaGFlue gas temperature sensord

Page 54

147A1 Main PCBA2 Power supply unitA3 OptolinkA4 Burner control unitA5 Programming unitA6 Coding cardDesignsExternal connection diagram5457 552 GBServi

Page 55 - Boiler water or

148A7 Connection adaptorA8 LON communication moduleA9 Internal extension H1S1 ON/OFF switchS2 Reset buttonX... Electrical interfaces!Outside temperatu

Page 56 - +20 14 5

149Spare parts informationQuote the part and serial no. (see typeplate) and the item number of therequired part (as per this parts list).Obtain standa

Page 57 - LON LON LON

155.4.7xElectrical connectionsInformation regarding the connection of accessoriesFor the connection, observe the separate installation instructions pr

Page 58

150100 O-ring 8 x 2 (5 pce.)102 Locking clip, condensate drain103 Drain plug (set)104 Cap105 Hose 7 10 x 1.5 x 750106 Union nut G 1110 Quick-action a

Page 59

151208061065070094062063069061074067206072071081066075068205092004003060064031Parts listsParts lists (cont.)5457 552 GBService

Page 60 - Instructing the system user

152007202204200208208207090090090005008140006113Parts listsParts lists (cont.)5457 552 GB

Page 61 - Calling up coding level 1

153303309304301305306307308302029097300315316315316112317Parts listsParts lists (cont.)5457 552 GBService

Page 62 - General/Group "1"

154013088015102016017002096082001011095040093092095010099021023099085034091085089032028141142096012103105104019094100117Parts listsParts lists (cont.)

Page 63

155054055114115131027 036 094134094035028051094038096055050056057142133138130137053 097052106087084039098099085084084080080105084110100Parts listsPart

Page 64 - Boiler/Group "2"

156025026024098084087080165167166164111037094084080080162171143163160030080033080080162089172Parts listsParts lists (cont.)5457 552 GB

Page 65 - DHW/Group "3"

157Setting and test val-ues Set value Commis-sioningService Date: By: Static pressure mbar max. 57.5 mbar Supply pressure (f

Page 66

158Rated voltage 230 VRated frequency 50 HzRated current 6 AProtection class IIP rating IP X 4 D toEN 60529Permissible ambient temperature during ope

Page 67

159Declaration of conformity for the Vitodens 222-FWe, Viessmann Werke GmbH&Co KG, D-35107 Allendorf, confirm as sole respon-sible body that the p

Page 68

16L 1LM1~L N230V~230V~3217654X3409620351001LNLNL1N2153DEBCA%aVG!?ARadio clock receiverBVitotrol 100 UTDB (only for constanttemperature control units)C

Page 69

160We, Viessmann Werke GmbH&Co KG, D-35107 Allendorf, confirm that the productVitodens 222-F complies with the NOx limits specified by the 1st BIm

Page 70

161AAcknowledging a fault display...102BBoiler draining DHW side...41Boiler temperature sensor...

Page 71

162IIgnition...36Ignition electrodes...36Ionisation electrode...

Page 73

164ApplicabilityCompact gas condensing boilerType FS2B from serial no.4.8 to 19 kW 7438 004 ... , 7438 007 ...6.5 to 26 kW 7438 005 ... , 7438 008 ...

Page 74

17Never interchange cores"L1" and "N". Install an isolator in the powersupply line that simultaneouslyisolates all non-earthed c

Page 75

18Routing the connecting cables!Please noteConnecting cables will be damaged if they touch hot parts.When routing and securing power cables on site, e

Page 76

191.4.2.5.3.2x6.Close control unit casing and insert pro-gramming unit, packed separately.NoteThe programming unit can also be usedin a wall mounting

Page 77

2Please follow these safety instructions closely to prevent accidents and mate-rial losses.Safety instructions explainedDangerThis symbol warns agains

Page 78

20Wall mounting base installationinstructionsInstallation sequenceClosing the control unit casing (cont.)5457 552 GB

Page 79

21For further information regarding the individual steps, see the page indicatedCommissioning stepsInspection stepsMaintenance steps Page• •1. Removin

Page 80

22Commissioning stepsInspection stepsMaintenance steps Page• •21. Checking the condensate drain and cleaning thesiphon...

Page 81

23Removing the front panelsSee page 11, steps 1 to 5.Filling the heating system!Please noteUnsuitable fill water increases the level of deposits and c

Page 82

24NoteIf the control unit has not beenswitched ON prior to filling the sys-tem, then the servomotor of thediverter valve will still be in its centralp

Page 83

25Selecting the language (if required) – only for weather-compen-sated control unitsNoteAt the commissioning stage, the displayis in German (default s

Page 84

26Venting the boiler1. Close the shut-off valves on the heat-ing water side.2. Remove cover panel A.3. Connect the drain hose on valve Bwith a drain.

Page 85

27Activating venting function with con-stant temperature control unit:1. Press OK and simultaneously forapprox. 4 s.2. Select "5" and c

Page 86

286. Check that the condensate pipe isconnected correctly to the siphon andheat exchanger.7. Refit cover panel.8. Secure control unit back in opera

Page 87

29Gas type conversion (only for operation with LPG)121. Set adjusting screw A at the gastrain to "2".2. Switch ON/OFF switch ON.3. Select

Page 88

3If you smell flue gasDangerFlue gas can lead to life-threat-ening poisoning. Shut down the heating system. Ventilate the boiler room. Close all do

Page 89

30 yes IgnitionnoFault EE Check the ignitionmodule (controlvoltage 230 Vacross plugs"X2.1" and "X2.2") yes

Page 90

31 yes Automatic calibra-tion of the com-bustion controllerno Fault Eb Initiate a heatdraw-off. Switchthe boiler OFF andON again.Press rese

Page 91

325. Start the boiler.NoteDuring commissioning, the boiler canenter a fault state because of airlocksin the gas line. After approx. 5 s,press the res

Page 92

334. "Change?" Select "Yes".A value flashes on the display (e.g."85"). In the delivered condition, thisvalue represents

Page 93

34Burner removal4x1. Switch ON/OFF switch at the con-trol unit and the main power supplyOFF.2. Close the gas shut-off valve and safe-guard against

Page 94 - Calling up the service menu

353. Pull electrical cables from fan motorA, gas valve B, ionisation elec-trode C, ignition unit D and earthtab E.4. Release gas supply pipe fitting

Page 95 - Brief scan

361. Remove electrodes B.2. Undo three retaining clips C at ther-mal insulation ring D and removethermal insulation ring D.3. Undo four Torx screws a

Page 96

371. Use a vacuum cleaner to remove res-idues from heat exchanger A insidethe combustion chamber. 2. If required, spray slightly acidic,chloride-fre

Page 97

38Checking the condensate drain and cleaning the siphonCBA1. Check that the condensate can drainfreely at the siphon.2. Pull retaining clip A off.3.

Page 98

391.2.AMagnesium anodeBEarth cableTesting the anode earth current with an anode testerNoteWe recommend that the magnesium anode function is checked an

Page 99

4Installation instructionsPreparing for installationProduct information...

Page 100 - Checking outputs (relay test)

401. Remove cover A.2. Pull earth lead B from tab C.3. Connect the tester (up to 5 mA) inseries between tab C and earthcable B. The anode is OK if t

Page 101

41Draining the boiler on the DHW side1. Connect hose to drain valve androute into a suitable container or drainoutlet.NoteEnsure adequate ventilation

Page 102 - Fault display

42Cleaning the primary storeNoteEN 806 specifies a visual inspection and (if required) cleaning every two years afterthe cylinder has been taken into

Page 103

43Checking and replacing the magnesium anode (if required)Check the magnesium anode. If it is discovered that the anode has degraded to 10to 15 mm Ø,

Page 104 - Fault codes

44Checking the diaphragm expansion vessel and system pressureNoteCarry out this test on a cold system.1. Drain the system, until the pressuregauge in

Page 105

45Checking the pre-charge pressure and the DHW expansion ves-sel (if installed)A1. Check the static pressure of the DHWline downstream of the pressur

Page 106

46NoteOperate the appliance with uncontaminated combustion air to prevent operatingfaults and damage.CO2 or O2 content The CO2 content must be within

Page 107

47Selecting the upper/lower output forweather-compensated control units:1. Press OK and simultaneously forapprox. 4 s.2. "Actuator test"

Page 108

48System version 1One heating circuit without mixer A143121Vitodens 222-F2Outside temperature sensor (onlyfor weather-compensated controlunits)3Vitotr

Page 109

49System version 2One heating circuit with mixer M2 and a low loss headerM3456712981Vitodens 222-F2Outside temperature sensor3Heating circuit with mix

Page 110

5Weather-compensated control unit... 127Internal extensions...

Page 111

50System version 3One heating circuit without mixer A1 and one heating circuit with mixer M2M3 45678121Vitodens 222-F2Outside temperature sensor3Heati

Page 112

51Function/system components CodeAdjust Delivered con-ditionOperation with LPG 82:1 82:0System only with one heating circuit with mixer withextension

Page 113

529Heat exchanger for system separa-tionqPAssembly kit with mixer (acces-sory)Function/system components CodeAdjust Delivered con-ditionOperation with

Page 114

534Heating circuit pump A15Heating circuit with mixer M2 (heat-ing circuit 2)6Flow temperature sensor M27Heating circuit pump M28Extension kit for one

Page 115 - 5457 552 GB

540.2Outside temperature in °CBoiler water orflow temperature in °CSlope2.42.62.83.03.23.4908070605040300 -5 -10 -15 -20510AB2.02.2Set room temperatur

Page 116 - Resistance in kΩ

55Changing the slope and levelABBoiler water orflow temperature in °C90+20 -20Outside temperature in °C3.51.40.2AChanging the slopeBChanging the level

Page 117

56Reduced room temperature +20 14 590-20D EACBExample 2: Adjustment of reduced roomtemperature from 5 °C to 14 °CABoiler water temperature or flowt

Page 118 - (cont.)

57Boiler control unit Vitotronic 200-H Vitotronic 200-H VitocomLON LON LONSubscriber no. 1Code "77:1"Subscriber no. 10Code "77:10"

Page 119

584. Select subscriber (e.g. subscriber10).The subscriber check for the selectedsubscriber is introduced. Successfully tested subscribersare designa

Page 120

59Constant temperature control unitReset code 24:1 to 24:0.NoteThe selected service parameters forhours run and time interval restart at 0.Commissioni

Page 121

6Vitodens 222-F, FS2BSet up for operation with natural gas E and LL.For conversion to LPG P (without conversion kit), see page 29.The Vitodens 222-F s

Page 122

60Fitting the front panels4.1.5.2.2x3.Instructing the system userThe system installer must hand the operating instructions to the system user andinstr

Page 123

61Note On weather-compensated controlunits, codes are displayed as plaintext. Codes that have no function due to theheating system equipment level o

Page 124 - Checking the fuse

62Select "General" for weather-compensated control units (see page 61).Select "1" for constant temperature control units (see page

Page 125

63Coding in the delivered condition Possible changeInternal circulation pump function51:0 Internal circulation pumpalways starts when thereis a heat d

Page 126 - Heating mode

64Coding in the delivered condition Possible changeSet flow temperature for ext. demand9b:70 Set flow temperature incase of external demand70 °C9b:0to

Page 127

65Select "DHW" for weather-compensated control units (see page 61).Select "3" for constant temperature control units (see page 61)

Page 128

66Parameter addressA5:...With heating circuit pump logic function: Heating cir-cuit pump "OFF"5 AT > RTset + 1 K6 AT > RTset7toAT >

Page 129 - Boosting DHW heating

67Coding in the delivered condition Possible changePump idle time, transition red. modeA9:7 With pump idle time:Heating circuit pump"OFF" if

Page 130 - Internal extensions

68Parameteraddress b5:...With heating circuit pump logic function:Heating circuit pump "OFF" Heating circuit pump "ON"6 RTactual &

Page 131

69Coding in the delivered condition Possible changeMax. pump speed in standard modeE6:... Maximum speed of thevariable speed heatingcircuit pump in %

Page 132 - Extension AM1

7100569464050cdefghklmnpab1405032036139841080q505955060055220330GCABFDEAHeating flow R ¾BDHW R ½CGas connection R ¾DCold water R ½EHeating return R ¾F

Page 133

70Coding in the delivered condition Possible changePump control in "Only DHW"F6:25 In the "Only DHW" oper-ating mode, the internal

Page 134 - Extension EA1

71Coding in the delivered condition Possible changeIncrease set flow temperatureFA:20 Raising the set boilerwater temperature or theset flow temperatu

Page 135

72Note In coding level 2, all codes are acces-sible, including the codes from codinglevel 1. Codes that have no function due to theheating system eq

Page 136 - Control functions

737. If you want to reset all codes totheir delivered condition:Select Ú "7" and confirm with OK.When " " flashes, confirm with O

Page 137 - External demand

74Coding in the delivered condition Possible change11:≠9No access to the codingaddresses for the com-bustion controller param-eters 11:9 Access open t

Page 138 - Screed drying function

75Coding in the delivered condition Possible change3A:0 Function input DE1 atextension EA1: No func-tion3A:1 Function input DE1: Heat-ing program chan

Page 139

76Coding in the delivered condition Possible change3b:0 Function input DE2 atextension EA1: No func-tion3b:1 Function input DE2: Heat-ing program chan

Page 140

77Coding in the delivered condition Possible change3C:0 Function input DE3 atextension EA1: No func-tion3C:1 Function input DE3: Heat-ing program chan

Page 141

78Coding in the delivered condition Possible change3F:0 Internal circulation pumpstays in control mode atsignal "Externaldemand"3F:1 Interna

Page 142 - Reducing the heat-up time

79Coding in the delivered condition Possible change79:1 With LON communicationmodule: Control unit isfault manager (only forweather-compensatedcontrol

Page 143

8Rated output range 4.8 to 19 kW 6.5 to 26 kW 8.8 to 35 kWd (mm) 1027 1027 1227e (mm) 1082 1082 1302f (mm) 1137 1137 1337g (mm) 1191 1191 1391h (mm) 1

Page 144

80Coding in the delivered condition Possible change8F:0 All control elementsactive8F:1 All control elements lockedout8F:2 Only standard settings canbe

Page 145

81Coding in the delivered condition Possible change9C:20 Monitoring LON subscrib-ers.If a subscriber fails torespond, the valuesspecified inside the c

Page 146 - Internal connection diagram

82Coding in the delivered condition Possible change21:0 No service interval (hoursrun) selected21:1to21:100The number of hours runbefore the burner sh

Page 147 - External connection diagram

83CodingCoding in the delivered condition Possible change56:0 Set DHW temperatureadjustable from 10 to60 °C56:1 Set DHW temperatureadjustable from 10

Page 148

84Coding in the delivered condition Possible change65:... Information regarding thetype of diverter valve (notadjustable):0: no diverter valve1: Vies

Page 149 - Parts lists

85CodingCoding in the delivered condition Possible changeA0:0 Without remote control(only for weather-com-pensated control units)A0:1 With Vitotrol 20

Page 150

86Coding in the delivered condition Possible changeA4:0 With frost protection (onlyfor weather-compensa-ted control units)A4:1 No frost protection; th

Page 151

87Coding in the delivered condition Possible changeA6:36 Extended economy func-tion disabled (only forweather-compensatedcontrol units)A6:5toA6:35Exte

Page 152

88Coding in the delivered condition Possible changeb0:0 With remote control:Heating mode/reducedmode: Weather-compen-sated (only for weather-compensat

Page 153

89Coding in the delivered condition Possible changeC5:20 Electronic minimum flowtemperature limit 20 °C(only for weather-com-pensated control units)C5

Page 154

9ML2. Prepare the DHW connections.Install the safety assembly (acces-sory or on-site provision) in accord-ance with DIN 1988 in the cold waterline (s

Page 155

90Coding in the delivered condition Possible changed8:0 No heating programchangeover via extensionEA1d8:1 Heating program change-over via input DE1 at

Page 156

91Coding in the delivered condition Possible changeE8:1 Minimum speed in opera-tion with reduced roomtemperature subject tothe setting in codingaddres

Page 157 - Commissioning/service reports

92Coding in the delivered condition Possible changeF6:25 In the "Only DHW" oper-ating mode, the internalcirculation pump is per-manently ON

Page 158 - Specification

93Coding in the delivered condition Possible changeFA:20 Raising the set boilerwater temperature or theset flow temperaturewhen changing fromoperation

Page 159 - Declaration of conformity

94Only for weather-compensated control unitsPress OK and å simultaneously forapprox. 4 s.Service menu overviewServiceDiagnosisActuator testCoding leve

Page 160

95Note"- - -" appears on the display if a sensor that has been scanned is faulty.Calling up operating dataWeather-compensated control unit1.

Page 161 - Keyword index

96Diagnosis Brief scan2:1:3:4:Select withØ0001 F000 0000 A000 0001 2000For an explanation of the relevant values in the individual lines and fields, s

Page 162

97Line (briefscan)Field 1 2 3 4 5 6 Heating circuit A1(without mixer)Heating circuit M2(with mixer)Heating circuit M3(with mixer)7: Remotecontrol0:

Page 163

98For explanations of individual scans, see the following table:Brief scan Display0 Systemschemes 1to 2Software versionControl unitSoftwareversionProg

Page 164 - Applicability

99Brief scan DisplayF2SoftwareversionOutput A1configura-tion(value corre-sponds tocode 33 set-ting)Output A1switchingstate0: OFF1: ONOutput A2configur

Commentaires sur ces manuels

Pas de commentaire