Installation and service
instructions
for contractors
VIESMANN
Vitodens 100-W
Type WB1B, 9.0 to 35.0 kW
Wall mounted gas fired condensing boiler
Natural gas and LPG version
Gas Council no.
41-819-12; 41-819-13; 41-819-14 (gas fired condensing boilers)
47-819-18; 47-819-19; 47-819-20 (gas fired condensing combi boil-
ers)
VITODENS 100-W
5366 836 GB 9/2008
Please keep safe.
Vue de la page 0
1 2 3 4 5 6 ... 67 68

Résumé du contenu

Page 1 - VIESMANN

Installation and serviceinstructionsfor contractorsVIESMANNVitodens 100-WType WB1B, 9.0 to 35.0 kWWall mounted gas fired condensing boilerNatural gas

Page 2 - Safety instructions

10BA DC E¨zzAHeating flow BGas fired condensing boiler:Cylinder flowGas fired condensing combi boiler:DHWCGas connectionDGas fired condensing boiler:C

Page 3

11Gas connectionA1. Connect gas shut-off valve to con-nection A.2. Carry out a leak/tightness test.!Please noteExcessive test pressure maydamage the

Page 4 - Service instructions

12Condensate connectionAConnect condensate drain A with aslope and a pipe vent to the publicsewer.Observe the local waste water regula-tions.NoteFill

Page 5 - Product information

13Balanced flue connectionConnect the balanced flue.During installation and positioning of theflue gas system, observe building regu-lations part L an

Page 6

14!Please noteElectronic modules can be dam-aged by electrostatic dis-charges.Touch earthed objects, such asheating or water pipes, to dis-charge stat

Page 7

15%Gas fired condensing boilers only:Cylinder temperature sensor (plugon the cable harness outside thecontrol unit) or connect the controlbox (supplie

Page 8

16Routing connecting cables and closing control unit!Please notePower cables will be damaged if they contact hot parts. When routing and securing powe

Page 9

17For further information regarding the individual steps, see the page indicatedCommissioning stepsInspection stepsMaintenance steps Page• • •1. Filli

Page 10 - Safety valve connection

18Filling the heating system!Please noteUnsuitable fill water increases the level of deposits and corrosion and maylead to boiler damage. Thoroughly

Page 11 - Gas connection

19closeopenB A4. Open shut-off valves A and (if instal-led) B.5. Fill the heating system via an externalfilling facility. (Minimum system pres-sure &

Page 12 - Filling the siphon with water

2Please follow these safety instructions closely to prevent accidents and mate-rial losses.Safety instructions explainedDangerThis symbol warns agains

Page 13 - Opening the control unit

20Venting the boiler by flushing out (after venting system)ABC1. Connect the drain hose on shut-offvalve A to a drain.2. Close shut-off valve B.3. Op

Page 14 - Electrical connections

21r2. Simultaneously turn rotary selectors"tw" and "tr" to their central posi-tion."SERV" appears on the display.rr3.

Page 15

22Checking the CO2 or O2 contentVitodens 100-W is factory-set for naturalgas. During commissioning or mainta-nance, the CO2 and CO have to bemeasured

Page 16

234. Adjust the upper output:Turn rotary selector "tr" to the con-trol range on the right.The display shows 5 bars for upperoutput.5. Meas

Page 17 - 5366 836 GB

24Burner removalDEAF 4xC B1. Switch OFF the power.2. Shut off the gas supply.3. Pull power cables from fan motorA, gas valve B and electrodesE.4. P

Page 18 - Filling the heating system

25Checking the burner gasket and the burner gauze assemblyCheck burner gasket A for damage and replace if required.Replace the burner gauze assembly i

Page 19

265. Refit thermal insulation ring C.Fixing screw torque: 3.5 Nm.6. Refit the electrode B.Fixing screw torque: 3.5 Nm.Checking and adjusting electrode

Page 20

27A1. Use a vacuum cleaner to remove res-idues from the heat exchanger Ainside the combustion chamber. 2. If required, spray slightly acidic,chlorid

Page 21

28Checking the condensate drain and cleaning the siphonAB1. Check that the condensate can drainfreely at the siphon.2. Remove all hoses from siphon A

Page 22 - content

29Burner installationCBDA 4xF E1. Install the burner and torque screwsA diagonally with 4.0 Nm.2. Insert new gasket and tighten the fit-tings on gas

Page 23

3If you smell flue gasDangerFlue gas can lead to life-threat-ening poisoning. Shut down the heating system. Ventilate the boiler room. Close all do

Page 24 - Burner removal

30Check gas equipment for tightness at operating pressureDangerEscaping gas leads to a risk ofexplosion.Check gas equipment for tight-ness.Fitting the

Page 25

31Instructing the system userThe system installer must hand the operating instructions to the system user andinstruct him/her in the operation of the

Page 26 - Cleaning the heat exchanger

32 Display screen Measures Control unit issuesa heat demand no Increase set valueand ensure heat isdrawn off yes F

Page 27

33 yes Burner in opera-tionnoStops below the setboiler water tem-perature andrestarts immedi-ately Check the flue gassystem for tight-ness

Page 28

34Fault codeon the dis-playSystem characteris-ticsCause Measures51 No DHW heating Outlet temperaturesensor shorted outCheck the sensor (seepage 43).52

Page 29 - Burner installation

35Fault codeon the dis-playSystem characteris-ticsCause MeasuresF2 Burner in a faultstateThe temperaturelimiter has respon-dedCheck the heating system

Page 30 - Fitting the front panel

36Fault codeon the dis-playSystem characteris-ticsCause MeasuresFd Burner blocked Burner control unitfaultCheck ignition electrodesand connecting cabl

Page 31 - Instructing the system user

37Removing front panel2.1.2x1. Release screws at the bottom of theboiler; do not remove completely.2. Remove front panel.Outside temperature sensor1

Page 32

38X21 X7X204 3 2 12. Disconnect cables from outside tem-perature sensor.10010-15-10-5 10 20 30Temperature in °C46820406080Resistance in kΩ03. Check

Page 33 - Fault messages on the display

39Boiler water temperature sensorA1. Pull the leads from boiler water tem-perature sensor A and check theresistance.TroubleshootingRepairs (cont.)536

Page 34

4Installation instructionsPreparing for installationProduct information...

Page 35

4010110 30 50 70 90 110Temperature in °C0.40.60.8246820Resistance in kΩ2. Check the sensor resistance andcompare it with the curve.3. In case of sev

Page 36

4110110 30 50 70 90 110Temperature in °C0.40.60.8246820Resistance in kΩ2. Compare the sensor resistance withthe curve.3. Replace the sensor in case

Page 37 - Outside temperature sensor

42A1. Pull the leads from temperature lim-iter A.2. Check the continuity of the tempera-ture limiter with a multimeter.3. Remove the faulty tempera

Page 38 - Resistance in kΩ

43Checking the outlet temperature sensor (gas fired condensingcombi boiler)A1. Pull the leads from outlet temperaturesensor A2. Check the sensor res

Page 39

44Checking the flue gas temperature sensorA1. Pull the leads from flue gas tempera-ture sensor A.2. Check the sensor resistance andcompare it with t

Page 40

4510110 30 50 70 90 110Temperature in °C0.40.60.8246820Resistance in kΩ3. Replace the sensor in case of severedeviation.Replacing flow limiter (gas f

Page 41

46Serial number (Type plate)Flow ratel/minColour7373 061 10 black7373 063 12 red7373 065 14 brownChecking or replacing the plate-type heat exchanger (

Page 42

473. Push the three-way valve drive Aslightly upwards.4. Turn the three-way valve B withdrive A 1/8 anticlockwise andremove.5. Remove two screws C fro

Page 43

483. Check fuse F4.TroubleshootingRepairs (cont.)5366 836 GB

Page 44

49Removing gas restrictorBFCADE3x1. Pull power cable from gas train A.2. Remove union nut B.3. Undo three screws C and removegas train A.Gas type conv

Page 45

5Vitodens 100-W, WB1BSet up for operation with natural gas.Preparing for installationPreparing the boiler installationDimensions and connections≥ 5≥ 2

Page 46

504. Remove gas restrictor D from gastrain.5. Fit gas train A with new gasketsE and F.Fixing screw torque C: 3 Nm.Union nut torque B: 22 Nm.6. Remove

Page 47 - Checking the fuse

514. Adjust the control unit to natural gasor LPG by turning the rotary selector"tw".The display shows: "0" for operation with n

Page 48 - (cont.)

52In weather-compensated mode, theboiler water temperature is regulatedsubject to the outside temperature.Heating curve of weather-compensated control

Page 49 - Removing gas restrictor

53MADEFGHKLBCAStepper motor diverter valveBIgnition/IonisationCVitotrol 100, type UTA or on-siteroom temperature controllerDesignsConnection and wirin

Page 50

54DVitotrol 100, type RT or on-siteroom temperature controllerEVitotrol 100, type UTD or on-siteroom temperature controllerFMains input 230V/50HzGRemo

Page 51

55When ordering spare parts:Quote the part and serial no. (see typeplate) and the item number of therequired part (as per this parts list).Obtain stan

Page 52 - Boiler water or

56082 Cable fixing102 Spray paint, Vitowhite103 Touch-up paint stick, Vitowhite104 Special grease110 Installation and service instructions111 Operatin

Page 53 - Connection and wiring diagram

57051050053058056052055054007057061100101056062Parts listsParts lists (cont.)5366 836 GBService

Page 54

58020017021003027004A010105016047014015015015047001005027012072011006027039073002027004047021013078018019040043043Parts listsParts lists (cont.)5366 8

Page 55 - Parts lists

59032039030041046044023035036033083037042048034040031040Parts listsParts lists (cont.)5366 836 GBService

Page 56

6EGas fired condensing boiler:Cylinder returnGas fired condensing combi boiler:Cold waterFHeating returnGDrain safety valve Rated output range kW 9 -

Page 57

60071009081070040Parts listsParts lists (cont.)5366 836 GB

Page 58

61Rated voltage: 230 V~Rated frequency: 50 HzRated current: 2.0 A~Safety class: IProtection: IP X4 to EN 60529Permissible ambient temperature durin

Page 59

62Gas fired condensing combi boiler, class II 2H3PRated output range in heatingmodeTV/TR 50/30 °CTV/TR 80/60 °CkWkW9 to 268.2 to 23.711 to 2610.0 to23

Page 60

63Declaration of conformity for the Vitodens 100-WWe, Viessmann Werke GmbH&Co KG, D-35107 Allendorf, confirm as sole respon-sible body that the pr

Page 61 - Specification

64BBoiler water temperature sensor ...39Burner gasket...25Burner gauze assembly...25Burner ins

Page 62

655366 836 GB

Page 65

68Viessmann LimitedHortonwood 30, TelfordShropshire, TF1 7YP, GBTelephone: +44 1952 675000Fax: +44 1952 675040E-mail: [email protected] W

Page 66

7Fitting the wall retainer250AØ10B155115AInstallation template VitodensBOpening for the balanced flue1. Position the supplied installation tem-plate

Page 67

83. Drill 710 mm holes and insert thesupplied rawl plugs.4. Fit wall retainer with screws sup-plied.Preparing the connections1. Prepare the water c

Page 68

9Removing the front panel and mounting the boiler2.3.1.2x1. Release screws at the bottom of theboiler; do not remove completely.2. Remove front pane