Control Overview—Combustion Air Control
Common Combustion Air Device Interface—System Boiler Connections
Applicable for Vitotronic 100, GC1
1 Call for heat demands from
individual boiler combustion
modules.
Note: All demand connections
are paralleled together
terminated in common
combustion air device interface.
2 Individual proving switch
signals provide damper/blower
status.
All individual connections come
from common combustion air
device interface.
3 Individual boiler combustion air
device adaptor. Mounted on
each boiler control DIN rail.
4 Air proving switch terminals on
each adaptor module. The
marking NO refers to Normally
Open.
5 Terminals which provide call for
combustion air device demand.
2
4 5
NO NO L L
Proving
Switch
Dry Contact
Activation
Section 3.5.6
Section 3
Connection Overview
IMPORTANT
Ensure that combustion air device is
suitable for intended application.
CAUTION
!
Provide disconnect means and over
current protection as required by local
codes.
IMPORTANT
A four-wire interconnection
between each boiler and the
common combustion air device
interface is required. This is a
120VAC circuit.
CAUTION
!
When making connections with
individual boiler interface adaptors,
ensure the power is turned off at the
boiler control.
5346540 v1.0 09/2006 Technical information subject to change without notice