Subject to changes due to technical improvements ESS Energie Systeme & Service GmbH
CHP accessory range – 01/2010 21
5368 463
Heating
5
5.6 Recirculating air damper
5.6.1 Recirculating air damper in proled tting for EM-18/36
Article number CHP module type ESS Viessmann
EM-18/36 710-00-0030 7411175
Function The recirculating air damper is used for room heating with warm extract air. On a controller, any
temperature from 10 to 35 °C can be set. Subject to room temperature, the damper servomotor constantly
opens or closes the louvre damper to regulate the set temperature.
Please note: In Germany, in accordance with the occupational safety directive, extract air must not be
routed into workrooms or other rooms people have access to!
Please note: If installed upstream of the optional extract air damper, machine/fan noise in the installation
room will be without attenuation!
Version
Fig. 5 Connection of the recirculating air damper to a CHP module EM-18/36
1 Branch 90° ID 315 mm, length 500 mm
2 Shut-off damper ID 315 mm, length 250 mm
3 Female connections
4 Fixing clamps 315 mm
5 Damper servomotor
6 Control unit with temperature sensor
7 Flanged collar ID 315 mm (module connection)
8 Plain ange ID 315 mm (module connection)
9 Hose ID 315 mm, length 500 mm (exible connector)
10 Hose clip
Pos. 7, 8 and 9 are part of the standard delivery of the CHP module
Pos. 4 and 10 on site
On-site requirements: 230 V supply
Delivery As loose accessories for on-site installation