Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
Boiler/burner
34:0 Signal "External
demand" on cir culation
pumps: All pu mps are
controlled
34:1
to
34:23
Signal "External demand"
on circulation pumps:
See the following table
Coding Internal
circulation
pump
Heating cir-
cuit pump
Heating cir-
cuit without
mixer
Heating cir-
cuit pump
Heating cir-
cuit with
mixer
Cylin der load ing pum p
0Control
funct.
Control
funct.
Control funct. Control funct.
1Control
funct.
Control
funct.
Control funct. OFF
2Control
funct.
Control
funct.
OFF Control funct.
3Control
funct.
Control
funct.
OFF OFF
4Control
funct.
OFF Control funct. Control funct.
5Control
funct.
OFF Control funct. OFF
6Control
funct.
OFF OFF Control funct.
7Control
funct.
OFF OFF OFF
8 OFF Control
funct.
Control funct. Control funct.
9 OFF Control
funct.
Control funct. OFF
10 OFF Control
funct.
OFF Control funct.
11 OFF Control
funct.
OFF OFF
12 OFF OFF Control funct. Control funct.
Code 2 (cont.)
46
Coding
5692 550 GB