Vitotronic 200 and 300-K Installation and Service
Coding 2 Vitotronic 200
“General” Group
Coding
Coding in the factory setting Possible change
00:0 -- 00:1
to
00:10
Do Not Adjust
11:9
No access to the coding
addresses for the combustion
controller parameters
11:9 Access open to the coding
addresses for the combustion
controller parameters.
2A:0 Without wireless outside
temperature sensor
2A:1 With wireless outside temperature
sensor (automatic recognition).
2A:2 Wireless outside temperature
sensor not used.
2D:0 Do Not Adjust -- --
30:3 When changing from a single
boiler to a multi boiler operation,
the coding address may
automatically reset to 30:3. To
prevent continuous boiler pump
operation, adjust the coding
address for each boiler to 30:0.
30:0 Coding address should be set
to 30:0, if not adjust to 30:0
32:0 Without extension AM1 32:1 With extension AM1 (automatic
recognition).
35:0 Without extension EA1 35:1 With extension EA1 (automatic
recognition).
36:0
Function, output aBJ at
extension EA1: Fault message
36:1
Function output aBJ: Accessories
pump.
36:2
Function output aBJ: DHW
recirculation pump.
39:2
Function output sA: Circulation
pump for DHW tank heating
39:0
Function output sA: DHW
recirculation pump.
39:1
Function output sA: Heating
circuit pump.
3A:0 Function input DE1 at extension
EA1: Not assigned
3A:1 Function input DE1: Heating
program - changeover.
3A:2 Function input DE1: External
demand with set supply
temperature. Supply temperature
setting: Coding address 9B.
Internal circulation pump
function: Coding address 3F.
3A:3 Function input DE1: External
blocking. Internal circulation pump
function: Coding address 3E.
3A:4 Function input DE1: External
blocking with fault message input
Internal circulation pump
function: Coding address 3E.
3A:5 Function input DE1: Fault
message input.
3A:6 Function input DE1: Brief
operation, DHW recirculation
pump (pushbutton function
DHW recirculation pump runtime
adjustment: Coding address 3D.
Select “General”