5608 487 v1.2
Vitocell 100-V Installation Instructions
Set-up and Connections
Temperature sensor installation for solar operation using
42 to 79 USG (160 to 300 L) tanks
42 to 79 USG (160 to 300 Liter) Tank Installation (continued)
Checking anode connections
Ensure the grounding wire is properly secured to the
magnesium anode.
Legend
A Magnesium anode
B Grounding wire
IMPORTANT
When connecting an externally powered anode to the top
flange lid, separate the magnesium anode in the bottom
flange lid from the grounding cable. The magnesium anode
may remain installed.
The temperature sensor for solar operation is included in
the solar control unit package.
The brass elbow with sensor well is available as an option
and must be used when solar connection is required.
1. For solar operation, install the sensor well into the
brass elbow and connect the assembly to the solar
return line.
2. Insert the temperature sensor until it bottoms out
inside the sensor well.
IMPORTANT
Never wrap insulating tape around the sensor. Do not
install solar tank sensor anywhere other than the brass
elbow with sensor well.