2 consumers, hydraulic connection via
valves:
System: 3
Hydraulic type: 3
Consumer 1 is heated via the external
heat exchanger.
According to the table on page 100 R3 is
the heat exchanger relay.
Primary pump (collector/ext. heat
exchanger) to R1 on and valve to R2
open:
S1S2 > "ΔTon"
Delivered condition 8 K (see
page 152)
Secondary pump (heat exchanger/con-
sumer 1) to R3 on:
S9S2 > "HE ΔTon"
Delivered condition 5 K (see
page 153)
Secondary pump (ext. heat exchanger/
consumer 1) to R3 off:
S9S2 > "HE ΔToff"
Delivered condition 3 K (see
page 153)
Make the following settings at the
solar control unit:
1. Main menu
"Solar"
"Options"
"System"
Set value "3".
"Hyd. Type"
Set value "3".
"Ext. HE"
Set "Yes".
2. Main menu
"Solar"
"Contractor"
"HE-cylinder"
Set value "1".
"Sen.HE.flow"
Set value "9".
3. Main menu
"Solar"
"Setting values"
"HE ΔTon"/"HE ΔToff"
Set a value.
Cooling function
This function can only be activated for
system 1 and 2.
Solar circuit pump and relay R3 on:
When the set temperature "Tcyl set"
has been reached and the start tem-
perature differential "ΔTon" is excee-
ded.
Solar circuit pump and relay R3 off:
When the selected stop temperature
differential "ΔToff" is not reached.
Make the following settings at the
solar control unit:
Main menu
"Solar"
"Options"
"Cooling fct."
Set "Yes".
Function description
External heat exchanger
(cont.)
5414 620 GB