2 consumers, hydraulic connection via
valves:
System: 3
Hydraulic type: 3
Consumer 1 is heated via the external
heat exchanger.
According to the table on page 100 R3 is
the heat exchanger relay.
Primary pump (collector/ext. heat
exchanger) to R1 on and valve to R2
open:
■
S1−S2 > "ΔTon"
Delivered condition 8 K (see
page 152)
Secondary pump (heat exchanger/con-
sumer 1) to R3 on:
■
S9−S2 > "HE ΔTon"
Delivered condition 5 K (see
page 153)
Secondary pump (ext. heat exchanger/
consumer 1) to R3 off:
■
S9−S2 > "HE ΔToff"
Delivered condition 3 K (see
page 153)
Make the following settings at the
solar control unit:
1. Main menu
■ "Solar"
■ "Options"
– "System"
Set value "3".
– "Hyd. Type"
Set value "3".
– "Ext. HE"
Set "Yes".
2. Main menu
■ "Solar"
■ "Contractor"
– "HE-cylinder"
Set value "1".
– "Sen.HE.flow"
Set value "9".
3. Main menu
■ "Solar"
■ "Setting values"
– "HE ΔTon"/"HE ΔToff"
Set a value.
Cooling function
■ This function can only be activated for
system 1 and 2.
■ Solar circuit pump and relay R3 on:
When the set temperature "Tcyl set"
has been reached and the start tem-
perature differential "ΔTon" is excee-
ded.
■ Solar circuit pump and relay R3 off:
When the selected stop temperature
differential "ΔToff" is not reached.
Make the following settings at the
solar control unit:
Main menu
■ "Solar"
■ "Options"
– "Cooling fct."
Set "Yes".
Function description
External heat exchanger
(cont.)
5414 620 GB