Viessmann VITOSOLIC 200 Instructions d'exploitation Page 48

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 172
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 47
48
DHW heating with mono-mode DHW cylinder and central heating
backup with multi-mode heating water buffer cylinder
Main components
Viessmann solar collectors
DHW cylinder Vitocell 100-V or
Vitocell 300-V
Multi-mode heating water buffer cylin-
der Vitocell 340-M or Vitocell 360-M
with integral DHW heating, with or
without stratification system
Vitosolic 200
Solar-Divicon
Wall mounted oil/gas boiler or oil/gas
boiler
Function description
DHW heating with solar energy
Solar circuit pump R1
eE
starts and
heating water buffer cylinder
rP
is
heated up if the temperature differential
between collector temperature sensor
S1
eQ
and cylinder temperature sensor
S2
rQ
is greater than the start tempera-
ture differential ΔTon.
Solar circuit pump R1
eE
is stopped in
accordance with the following criteria:
Actual temperature dropping below
the stop temperature differential ΔToff
Exceeding the electronic temperature
limit of control unit
eZ
(max. 90 °C)
Reaching the temperature selected at
high limit safety cut-out
rR
(if installed)
Entire heating water buffer cylinder
rP
is
heated by the solar thermal system if the
insolation is adequate for DHW heating.
If there is inadequate solar energy, the
DHW in the lower part of heating water
buffer cylinder
rP
is preheated by solar
energy, and heated to the required tem-
perature in DHW cylinder
qP
by boiler
1
.
A temperature-controlled DHW stratifi-
cation is not possible.
DHW heating without solar energy
DHW cylinder
qP
is heated by
boiler
1
. The cylinder thermostat with
cylinder temperature sensor
3
of boiler
control unit
2
regulates the circulation
pump for cylinder heating
4
.
Central heating with solar energy
Three-way diverter valve R6
rZ
is
switched to position "AB-A" and the heat-
ing return water is routed to boiler
1
via
heating water buffer cylinder
rP
, if the
temperature differential between buffer
cylinder temperature sensor S5
rW
and
heating circuit return temperature sensor
S6
rT
exceeds start temperature differ-
ential ΔT6on. If the temperature of the
preheated return water is too low, boiler
1
reheats the water to the required flow
temperature. Three-way diverter valve
R6
rZ
is switched to position "AB-B" if
the actual temperature falls below the
stop temperature differential ΔT6off.
System examples
System example 7
5414 620 GB
Vue de la page 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 171 172

Commentaires sur ces manuels

Pas de commentaire