Coding
Coding in the delivered condition Possible change
35:4 4 boilers connected to the
Vitotronic 300-K.
35:1
to
35:8
1 to 8 boilers connected to
the Vitotronic 300-K.
36:0 Electronic minimum sys-
tem flow temperature limit
set to 0 °C.
36:1
to
36:127
Minimum limit adjustable
from 0 to 127 °C.
37:80 Electronic maximum sys-
tem flow temperature limit
set to 80 °C.
37:20
to
37:127
Maximum limit adjustable
from 20 to 127 °C.
Note
Value must not be higher
than the lowest value of
coding address "06" in the
"Boiler" group of every
Vitotronic 100.
38:0 No lead boiler or boiler
sequence changeover;
see function description
in chapter "Cascade con-
trol".
38:1 Lead boiler changeover:
Every first day of the
month, the boiler with the
shortest number of hours
run by its burner becomes
the lead boiler.
38:2
to
38:200
Lead boiler changeover
after 200 to 20,000 hours
run;
1 step
100 hours run.
39:0 No permanent lead
boiler.
39:1
to
39:8
Permanent lead boiler is
boiler ...
3A:0 No permanent last
boiler.
3A:1
to
3A:8
Permanent last boiler is
boiler ...
3b:1 Standalone parallel
boiler circuit:
With flow temperature
sensor (see page 64).
3b:0 Standalone parallel boiler
circuit:
Without flow temperature
sensor (see page 64).
3b:2 Standalone serial boiler
circuit:
Code 2, Vitotronic 300-K
"Cascade" group
5601 090 GB