Coding in the delivered condition Possible change
Without flow temperature
sensor (see page 64).
3C:0 Condensing strategy
(see page 66).
3C:1 Conventional boiler strat-
egy 1 (see page 67).
3C:2 Conventional boiler strat-
egy 2 (see page 68).
3d:1 Output statement for con-
densing strategy and
conventional boiler strat-
egy 1.
3d:0 No output statement.
Note
Vitotronic 300-K regulates
only according to conven-
tional boiler strategy 2.
3E:0 Distribution pump will
only run if heat demand
exists.
3E:1 Distribution pump always
runs; shutdown through
"External blocking" signal.
3F:0 Without cylinder priority
control for distribution
pump.
3F:1 With cylinder priority con-
trol for distribution pump.
41:31 No ECO threshold
boiler 1.
41:30
to
41:+30
ECO threshold boiler 1
adjustable from
30 to
+30 °C.
42:31 No ECO threshold
boiler 2.
42:30
to
42:+30
ECO threshold boiler 2
adjustable from
30 to
+30 °C.
43:31 No ECO threshold
boiler 3.
43:30
to
43:+30
ECO threshold boiler 3
adjustable from
30 to
+30 °C.
44:31 No ECO threshold
boiler 4.
44:30
to
44:+30
ECO threshold boiler 4
adjustable from
30 to
+30 °C.
45:60 Start integral threshold
set to 60 K x min.
45:1
to
45:255
Start integral threshold
adjustable from 1 to
255 K x min.
Note
If the threshold is excee-
ded, one boiler or one
burner stage is switched
on.
Code 2, Vitotronic 300-K
"Cascade" group
(cont.)
5601 090 GB
Service