DHW cylinder goes cold:
Set value –2.5 K, adjustable via coding
address "59"
or
Actual DHW temperature at sensor 2
< set DHW temperature x factor for
start time (adjustment via coding
address "69")
The DHW cylinder is hot:
Set value +2.5 K
and
Actual DHW temperature at sensor 2
> set DHW temperature x factor for
stop time (adjustment via coding
address "68")
Code "55:3" in the "DHW" group, cyl-
inder temperature control, primary
store system
The DHW cylinder goes cold (set value
–2.5 K; adjustable via coding address
"59"):
The common set flow temperature is
set 20 K higher than the set DHW tem-
perature (change via coding address
"60").
The primary pump in the primary store
system starts.
The 3-way mixing valve opens and
then regulates to the specified set
value.
The circulation pump for cylinder heat-
ing cycles (briefly switches on and off)
until the set flow temperature has been
reached (set DHW temperature + 5 K).
Then it runs constantly.
If, during heating, the actual value falls
below the required set temperature,
the circulation pump for cylinder heat-
ing will temporarily cycle again.
The DHW cylinder is hot:
(Cylinder temperature sensor 1:
Actual value
set value
and
cylinder temperature sensor 2:
Actual value > set value –1.5 K):
The common set flow temperature is
returned to the set weather-compen-
sated value.
The circulation pump for cylinder heat-
ing stops immediately when the
3-way mixing valve is fully opened.
or
The circulation pump for cylinder heat-
ing stops after expiry of the run-on time
that is selected via code "62".
Function description, Vitotronic 100 and Vitotronic 300-K
Cylinder temperature control
(cont.)
5601 090 GB