Displayed
fault code
System characteris-
tics
Cause Measures
bE Control mode without
remote control.
Communication
fault, Vitotrol
remote control with
mixer M3 (heating
circuit 3)
Check connections, lead
(see separate installation
and service instructions)
and coding address "A0"
in the "Heating cir-
cuit..." group.
With wireless remote con-
trol:
Place the remote control
near the wireless base
station and check connec-
tion.
bF Control mode.
No communication
via LON.
Incorrect LON
communication
module
Replace LON communi-
cation module.
C2 Control mode. Lead break, KM
BUS to solar con-
trol module or
Vitosolic
Check KM BUS cable and
device.
Without solar control unit:
Set code "54:0" in the
"General" group.
CF Control mode.
No communication
via LON.
Communication
fault, control unit
LON communica-
tion module
Check LON communica-
tion module and replace if
required.
If no LON communication
module is installed, set
code "76:0" in the "Gen-
eral" group.
d3 Control mode. Communication
fault, exten-
sion EA1
Check connections (see
page 137).
Without extension EA1:
Set code "5b:0" in the
"General" group.
d5 Boiler ramps to the
electronic maximum
boiler water tempera-
ture limit.
Boiler does not log
in at the cascade
control unit
Check communication via
subscriber check, leads/
cables to the
Vitotronic 100 and codes.
d6 Control mode. Input DE1 at exten-
sion EA1 reports a
fault
Remove fault at appliance
concerned.
Troubleshooting, Vitotronic 300-K
Fault codes
(cont.)
5601 090 GB