Control sequence
Code "55:0" in the "DHW" group, cyl-
inder heating
The DHW cylinder goes cold (set value
–2.5 K; adjustable via coding address
"59"):
The common set flow temperature is
set 20 K higher than the set DHW tem-
perature (change via coding address
"60").
The DHW cylinder is hot (set value
+2.5 K):
The common set flow temperature is
returned to the set weather-compen-
sated value.
Pump run-on:
The circulation pump runs on after cyl-
inder heating until one of the following
criteria is met:
The weather-compensated set flow
temperature has been reached.
The set DHW temperature is excee-
ded by 5 K.
The set max. run-on time is reached
(coding address "62").
Without pump run-on (code "62:0")
Code "55:1" in the "DHW" group,
adaptive cylinder heating
With adaptive cylinder heating, the
speed of the temperature rise during
DHW heating is taken into account.
The DHW cylinder goes cold (set value
–2.5 K; adjustable via coding address
"59"):
The common set flow temperature is
set 20 K higher than the set DHW tem-
perature (change via coding address
"60").
The DHW cylinder is hot:
The control unit checks whether the
boiler will be required to supply heating
energy after the cylinder has been
heated up or whether residual boiler
heat should be transferred to the DHW
cylinder.
Accordingly, the control unit deter-
mines the burner and circulation pump
stop times to prevent the set DHW
temperature being substantially
exceeded after the cylinder has been
heated up.
Code "55:2" in the "DHW" group, cyl-
inder temperature control with 2 cyl-
inder temperature sensors
Cylinder temperature sensor 1 enables
the circulation pump for cylinder heating
and is evaluated for stop conditions dur-
ing the pump run-on time.
Cylinder temperature sensor 2:
Cylinder heating will start early if a lot of
hot water is drawn off. Cylinder heating
will terminate early if no hot water is
drawn off.
Function description, Vitotronic 100 and Vitotronic 300-K
Cylinder temperature control
(cont.)
5601 090 GB