56
Displayed
fault code
System characteris-
tics
Cause Measures
8E Control mode. Communication
fault, Vitotronic 100
of boiler 3
Check and replace cas-
cade communication
module and connecting
cable if required.
8F Control mode. Communication
fault, Vitotronic 100
of boiler 4
Check and replace cas-
cade communication
module and connecting
cable if required.
90 Control mode. Short circuit, tem-
perature sen-
sor
/
,
connection at solar
control module.
Check temperature sen-
sor
/
(see separate
installation and service
instructions).
91 Control mode. Short circuit, tem-
perature sensor
,
connection at solar
control module.
Check temperature sen-
sor
(see separate
installation and service
instructions).
92 No solar DHW heat-
ing.
Short circuit, col-
lector temperature
sensor,
connection of tem-
perature sensor
&
at solar control
module or sensor
at S1 of the
Vitosolic.
Check sensor at the solar
control unit (see separate
installation and service
instructions).
93 Control mode. Short circuit, tem-
perature sensor,
connection to S3 of
the Vitosolic.
Check sensor at the solar
control unit (see separate
installation and service
instructions).
94 No solar DHW heat-
ing.
Short circuit, cylin-
der temperature
sensor,
connection of tem-
perature sensor
%
at solar control
module or sensor
at S2 of the
Vitosolic.
Check sensor at the solar
control unit (see separate
installation and service
instructions).