Coding
Coding in the delivered condition Possible change
01:1 Single boiler system 01:2 Multi boiler system with
cascade control via LON
01:3 Never adjust
02:1 Type GC1B:
Two-stage burner
02:0 Single stage burner
02:2 Modulating burner
03:0 Type GC1B:
Gas operation
03:1 Oil operation (irreversible)
03:2 Set automatically if no boil-
er coding card or an incor-
rect boiler coding card is in-
serted.
04:... Type GC1B:
Switching hysteresis,
burner:
Delivered condition de-
faulted by the boiler cod-
ing card.
04:0 Switching hysteresis 4 K
(see page 98)
04:1 Switching hysteresis sub-
ject to heat demand (see
page 98)
ERB50 function (values
from 6 to 12 K)
04:2 ERB80 function (values
from 6 to 20 K)
05:... Type GC1B:
Modulating burner:
Burner curve
Delivered condition de-
faulted by the boiler cod-
ing card.
05:0 Linear burner curve
05:1
to
05:99
Non-linear burner curve
(P
T
: P
max
)·100
P
T
in kW: Partial output at
⅓ of the actuator runtime
P
max
in kW: Maximum out-
put
06:87 Maximum limit of the boil-
er water temperature set
to 87 °C.
06:20
to
06:127
Maximum limit adjustable
from 20 to 127 °C.
Observe the temperature
controller settings.
07:1 Consecutive boiler num-
ber in multi boiler sys-
tems
07:2
to
07:4
Consecutive boiler number
in multi boiler systems
08:... Type GC1B:
Maximum burner output
in kW
08:0
to
08:199
Maximum output adjusta-
ble from 0 to 199 kW.
Code 2, Vitotronic 100
Group 2
5815 091 GB
Service