Note
Vitotronic 100:
During the subscriber check, the dis-
play for the relevant subscriber flashes
for approx. 1 min.
Vitotronic 200-H:
During the subscriber check, the dis-
play for the relevant subscriber flashes
the subscriber no. for approx. 1 min
and displays "Wink".
Checking actuators and sensors
Vitotronic 100
Carrying out a relay test
Service menu:
1. Press OK and å simultaneously for
approx. 4 s.
flashes on the display.
2. Press to select . OK to confirm
Note
Before an actuator is selected, all
actuators are switched to zero volt.
3. / for the required actuator (output),
see the following table.
4. OK to confirm
The display shows the number for the
activated actuator and "ON".
The following relay outputs can be controlled subject to the system equipment
level:
Display Explanation
0 All actuators have been switched off.
Stepped burner:
1 Burner ON or burner stage 1 ON
2 Burner stage 1 and 2 ON
Modulating burner:
1 Modulation controller open
2 Modulation controller neutral
3 Modulation controller close
5
Actuator at output on
Commissioning, Vitotronic 100 and Vitotronic 300-K
Connecting the control unit to the LON
(cont.)
5815 091 GB
Service