Analogue input 0 – 10 V
The 0 – 10 V hook-up provides an addi-
tional set flow temperature:
0 – 1 V is seen as "no set flow temper-
ature".
Note
Ensure DC separation between the LV
output and the earth conductor of the on-
site power supply.
Coding address "1E" in the "General"
group:
"1E:0" temperature demand adjust-
able in the range from 0 to 100 °C
1 V
10 °C set value change
10 V
100 °C set value change
"1E:1" temperature demand adjust-
able in the range from 30 to 120 °C
1 V
30 °C set value change
10 V
120 °C set value change
Output
aBJ
Connection of a central fault messaging
facility or signalling reduced mode
(reduction of the heating circuit pump
speed).
Select the function of output
aBJ
at cod-
ing address "5C" in the "General"
group.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K
EA1 extension
(cont.)
5815 091 GB