Note
At coding level 2, all codes are acces-
sible, including the codes at coding
level 1.
Codes that have no function due to the
heating system equipment level or the
setting of other codes are not dis-
played.
Heating systems with one heating cir-
cuit without mixer and one or two heat-
ing circuits with mixer:
The heating circuit without mixer is
designated "Heating circuit 1" and
the heating circuits with mixer as
"Heating circuit 2" or "Heating cir-
cuit 3".
If the heating circuits were given indi-
vidual designations, the selected des-
ignation and "HC1", "HC2" or "HC3"
appear instead.
For code groups, see page 130.
Service menu:
1. Press OK and simultaneously for
approx. 4 s.
2. Press OK and simultaneously for
approx. 4 s.
3. "Coding level 2"
4. / for the group of the required cod-
ing address
5. / for the required coding address
6. / for the required value according to
the following tables
Note
The system exits the service menu auto-
matically after 30 min.
Resetting all codes to their delivered condition
Select "Standard setting" in coding
level 2.
Note
This also resets codes at coding
level 1.
"General" group
Coding
Coding in the delivered condition Possible change
00:1 One heating circuit with-
out mixer A1 (heating cir-
cuit 1), without DHW
heating
00:2
to
00:10
For system schemes, see
the following table
Code 2, Vitotronic 300-K
Calling up coding level 2
5815 091 GB