Deleting fault history
While the list is displayed, press OK until
flashes. OK to confirm.
Fault codes
Displayed
fault code
System characteris-
tics
Cause Measures
0F Control mode Service
"0F" is only dis-
played in the fault
history.
Service the appliance.
Note
After a service set code
"24:0" in group 2.
30 Type GC1B:
The burner is started
and stopped via the
temperature control-
ler.
Short circuit, boiler
water temperature
sensor
Check boiler water tem-
perature sensor (see
page 185).
38 Type GC1B:
The burner is started
and stopped via the
temperature control-
ler.
Lead break, boiler
water temperature
sensor
Check boiler water tem-
perature sensor (see
page 185).
60 Type GC1B:
Boiler with maximum
temperature, no out-
put reduction, mixing
valve return tempera-
ture control open
Type GC4B:
Boiler at maximum
temperature
Short circuit, tem-
perature sensor
aJA
Type GC1B
Check temperature sen-
sor (see page 185).
Type GC4B:
Remove temperature
sensor.
Without temperature sen-
sor:
Set code "4A:0" in
group 1.
Troubleshooting Vitotronic 100
Fault display
(cont.)
5815 091 GB
Service