Central heating with solar energy
Three-way diverter valve R6
rZ
is
switched to position "AB-A" and the heat-
ing return water is routed to boiler
1
via
heating water buffer cylinder
rP
, if the
temperature differential between buffer
cylinder temperature sensor S5
rW
and
heating circuit return temperature sensor
S6
rT
exceeds start temperature differ-
ential ΔT6on. If the temperature of the
preheated return water is too low,
boiler
1
reheats the water to the
required flow temperature. Three-way
diverter valve R6
rZ
is switched to posi-
tion "AB-B" if the actual temperature falls
below the stop temperature differential
ΔT6off.
Central heating without solar energy
Three-way diverter valve R6
rZ
remains
at zero volt (position "AB-B") if the tem-
perature differential between buffer cyl-
inder temperature sensor S5
rW
and
heating circuit return temperature sensor
S6
rT
is less than temperature differen-
tial ΔT6off. There will be no flow through
heating water buffer cylinder
rP
.
Boiler
1
supplies the heating circuit
with heat according to the heating curve
set at boiler control unit
2
.
A low loss header
6
with flow temper-
ature sensor
5
is required in conjunc-
tion with a wall mounted oil/gas
boiler.
System examples
System example 6
(cont.)
5414 620 GB