Required settings on the solar control unit
Main menu Delivered
condition
Setting
Operator code 0000 0200
Solar options
System (see page 95) 1 1
Set solar values
Tcylset (set cylinder temperature) 60 °C
ΔTon (start temperature differential for solar circuit
pump R1
eE
)
8.0 K
ΔToff (stop temperature differential for solar circuit
pump R1
eE
)
4.0 K
System options
Add. fct.
(Additional function for DHW heating)
No Yes
Thermost. 2, function block 1, see page 112) No Yes
ΔT Fct5 (ΔT function for switching discharge pump
(heating water buffer cylinder) R3
qI
, function block
1, see page 112)
No Yes
Thermost. 4, function block 2, see page 112) No Yes
ΔT Fct6 (ΔT function for switching the primary pump
(preheating cylinder) R6
qR
, function block 2, see
page 112)
No Yes
Set system values
Th2on (start temperature for R3) 40 °C Value at the
mixing valve
qO
10 K
Th2off (stop temperature for R3) 45 °C Value at the
mixing valve
qO
7K
ΔT5on (start temperature differential for R3) 5.0 K 10 K
ΔT5off (stop temperature differential for R3) 3.0 K 6 K
Th4on (start temperature for R6) 40 °C Value at the
mixing valve
qO
10 K
Th4off (stop temperature for R6) 45 °C Value at the
mixing valve
qO
7 K
ΔT6on (start temperature differential for R6) 5.0 K 10 K
ΔT6off (stop temperature differential for R6) 3.0 K 6 K