4. Scan actual temperature of the rele-
vant sensor.
Adjusting the heating curve
The heating curves illustrate the relation-
ship between the outside temperature
and the boiler water or flow tempera-
ture.
To put it simply: The lower the outside
temperature, the higher the boiler water
or flow temperature.
The room temperature, in turn, depends
on the boiler water or flow temperature.
Settings in the delivered condition:
Slope = 1.4
Level = 0
Note
If the heating system includes heating
circuits with mixers, then the flow tem-
perature of the heating circuit without
mixer is higher by a selected differential
(8 K in the delivered condition) than the
flow temperature of the heating circuits
with mixers.
The differential temperature is adjusta-
ble via coding address "9F" in the "Gen-
eral" group.
0.2
Outside temperature in °C
Boiler water or
Flow temperature in °C
Slope
2.4
2.6
2.8
3.0
3.2
3.4
90
80
70
60
50
40
30
0 -5 -10 -15 -20510
2.0
2.2
Set room temperature in °C
35
30
25
20
15
10
5
0.4
0.6
0.8
1.0
1.2
1.4
-30-25
1.8
1.6
Commissioning
Testing actuators and sensors on the Vitotronic…
(cont.)
5601 090 GB
Service