Slope setting ranges:
Underfloor heating systems: 0.2 to 0.8
Low temperature heating systems: 0.8
to 1.6
Selecting the set room temperature
Individually adjustable for each heating
circuit.
The heating curve is offset along the axis
of the set room temperature. When the
heating circuit pump logic function has
been enabled, the curve modifies the
starting and stopping characteristics of
the heating circuit pump.
Standard set room temperature
90
-20
26 + 20
A
C
D
E
B
Example 1: Change in the standard set
room temperature from 20 to 26 °C
A
Boiler water temperature or flow
temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Changing the standard set room temper-
ature
Operating instructions
Reduced set room temperature
+20 14 5
90
-20
D E
A
C
B
Example 2: Change in the reduced set
room temperature from 5 °C to 14 °C
A
Boiler water temperature or flow
temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Changing the reduced set room temper-
ature
Operating instructions
Changing the slope and level
Individually adjustable for each heating
circuit.
Commissioning
Adjusting the heating curve
(cont.)
5601 090 GB