Removing the front panels
Danger
Touching 'live' components can
result in the transfer of danger-
ous body currents.
Never touch the connections
inside the control panel or in
the control module below.
Danger
The absence of earthing on the
components can transfer dan-
gerous body currents and may
damage the equipment, should
an electrical fault occur.
Always re-connect the earth
strap when re-fitting the cover.
!
Please note
To prevent equipment damage,
wait at least 30 min between
the installation and the com-
missioning of the equipment.
Work on the refrigeration cir-
cuit must only be carried out
by a qualified refrigeration
engineer.
Observe the operating instruc-
tions when commissioning the
equipment.
Remove the front panels for commis-
sioning, inspection and maintenance
work.
Maintaining service reports
Enter measurements taken during
commissioning described in the fol-
lowing in the reports from page 216
onwards.
Checking the refrigerant circuit for leaks
Check the heat pump interior with a
refrigerant leak detector or leak detec-
tion spray for refrigerant leaks.
1. Remove the front panels (see
page 56).
2. Remove the front part of the heat
pump thermal insulation (see
page 59).
3. Check the floor area, valves and all
visible solder joints of the heat
pump for traces of oil.
Further details regarding the individual steps
101
Commissioning, inspection, maintenance
5592 969 GB
Service