Note
This setting is only used if parameter set "1" (free parameters) has been
selected under "Cooling mixer parameters".
For function description see page 181.
Access
&
"Device settings"
&
"Programming"
&
"Heating circuit"
&
"Heating circuit 1/2"
&
"NC mixer active zone"
&
(%/5)
&
or
&
"NC mixer dead zone"
&
(=/0)
Standard setting Setting range
"NC mixer active zone" 4.0 K 2.0 to 40 K
"NC mixer dead zone" 1.0 K 0.5 to 3.0 K
Cooling mixer runtime
Note
This setting is only used if parameter set "1" (free parameters) has been
selected under "Cooling mixer parameters".
Setting of the time required by the servomotor of the cooling mixer for a com-
plete changeover from one operating state into another (90 degree movement).
Runtimes that are too short, can lead to the cooling mixer "Cycling".
Access
&
"Device settings"
&
"Programming"
&
"Heating circuit"
&
"Heating circuit 1/2"
&
"Cooling mixer runtime"
&
(m/l)
Standard setting 0:10 min
Setting range 0:05 to
4:15 min
Active zone/dead zone natural cooling mixer
185
Heating circuit control settings