The heating limit temperature defines the value of the outside temperature
below which central heating commences.
The heating limit temperature is the result of the selected set room temperature
less the value entered under "Heating limit < T room".
Example:
The selected set room temperature is 20 °C, the value entered under "Heating
limit < T room" is 4.0 K.
Central heating commences if the average outside temperature drops below
16 °C (heating limit temperature).
If the outside temperature exceeds 18 °C, central heating is adjusted because
of the specified hysteresis of 2 K.
A Set room temperature
B Outside temperature
C Selected value "Heating limit < T
room"
D Heating OFF
E Heating ON
Access
&
"Device settings"
&
"Programming"
&
"System definition"
&
"Heating limit < T room"
&
(1/!)
Standard setting 4 K
Setting range 0 to 20 K
Temperature limit for reduced temperature mode
The "reduced" temperature mode (see operating instructions) will no longer be
used, if the average outside temperature falls below the temperature limit
selected here. The equipment heats up to the temperature selected for standard
operation.
Operation will continue in accordance with the selected switching times, if the
average outside temperature stays above this temperature limit.
Commentaires sur ces manuels