Access
&
"Device settings"
&
"Programming"
&
"Further menu items"
&
"Buffer cylinder"
&
"Max. temperature" (1/!)
Standard setting 60 °C
Setting range 1 to 70 °C
Stop optimisation
Note
This function is only available in case of system design 2, if the option "Yes"
was selected under "Buffer cylinder" (see page 187).
The stop optimisation ensures that, with the selected switching times (see oper-
ating instructions), the buffer cylinder is always fully heated at the end of stan-
dard mode.
Access
&
"Device settings"
&
"Programming"
&
"Further menu items"
&
"Buffer cylinder"
&
"Stop optimisation"
&
("YES"/"NO")
Standard setting YES
Setting range YES/NO
Excess reaction
Note
This function is only available in case of system design 2, if the option "Yes"
was selected under "Buffer cylinder" (see page 187).
Coordination of the heat drawn off in the secondary circuit when the heat pump
produces an excess of heat or the heat drawn by the secondary circuit is sud-
denly choked off.
Settings:
0 No heat drawn off
1 Heat will be drawn off only in case of a critical excess, i.e. if critical tem-
peratures were reached in the heat pump circuit or the minimum heat
pump runtime has not yet been reached.
Maximum temperature (cont.)
189
Buffer cylinder control settings
5592 969 GB