Viessmann VITOCAL 222-G Fiche technique Page 131

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 236
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 130
3. Check whether there is voltage at
the power feed to the control unit/
electronics; provide power if
required.
4. Check the plug-in and threaded
connections.
5. Replace the power supply unit.
6. Replace the programming unit.
7. Replace the main PCB.
Refrigerant circuit service valves
!
Please note
If work on the refrigerant circuit is carried out incorrectly, there is a risk of
equipment damage.
The following steps must only be carried out by authorised contractors.
Opening the service valve
When removing the sealing cap A
counterhold the hexagon C with a
spanner.
Diagnosis (cont.)
131
Troubleshooting
5592 969 GB
Service
Vue de la page 130
1 2 ... 126 127 128 129 130 131 132 133 134 135 136 ... 235 236

Commentaires sur ces manuels

Pas de commentaire