Control unit power supply
A Terminals in the control panel
Note
This supply must never be blocked.
Max. protection 16 A.
Compressor power supply
A Terminals at the control module
Recommended core cross-section:
1.5 mm
2
Note
The upstream fuses must have Z
characteristics.
Instantaneous heating water heater power supply
A Terminals in the control panel
Max. fuse rating 16 A
Recommended core cross-section:
&
6 kW: 1.5 mm
2
&
9 kW: 2.5 mm
2
The three heating elements are
switched by inserting jumpers across
X60.8, X60.9 and X60.10 in star for-
mation and must be connected to N.