A Flow temperature
B Differential between set room
temperature and outside tempera-
ture
C Heating curve
D Possible positive correction range
(0.1 to 10.0 K)
E Possible negative correction
range
(0.1 to 10.0 K)
Access
&
"Device settings"
&
"Programming"
&
"Heating circuit"
&
"Heating circuit 1/2"
&
"Max. flow corr." (0/=)
Standard setting 10.0 K
Setting range 0.1 to 10.0 K
Room temperature control
A room temperature-dependent control is possible subject to a room tempera-
ture sensor being installed and enabled. This function must be activated for
this.
Note
If "Yes" is selected for room control, the level and slope of the heating curve can
no longer be adjusted (weather-compensated control unit parameters).
Access
&
"Device settings"
&
"Programming"
&
"Heating circuit"
&
"Heating circuit 1/2"
&
"Room temperature control"
("YES"/"NO")
Standard setting NO
Setting range YES/NO
Maximum flow temperature correction (cont.)
177
Heating circuit control settings
5592 969 GB