Viessmann VITOCAL 222-G Fiche technique Page 225

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 236
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 224
Vitocal 242-G/222-G Type BWT 106 BWT 108 BWT 110
Connections
Primary flow and return
(brine)
optionally Rp ¾" or Multi-connect system
DN 20
Heating flow and return Multi-connect system DN 20
Solar flow and return (only
with Vitocal 242)
Multi-connect system DN 20
Cold water, DHW R ¾" ¾" ¾"
DHW circulation R ¾" ¾" ¾"
Drain (overflow) DN 32 32 32
DHW cylinder
Capacity l 250 250 250
Continuous DHW output l/h 200 200 200
DHW performance factor
N
L
1.5 1.5 1.5
Max. draw-off rate at the
stated DHW performance
factor N
L and DHW heating
from 10 to 45 °C
l/min 16.8 16.8 16.8
Connectable collector area (only
for the Vitocal 242)
&
Vitosol 200-F m
2
5 5 5
&
Vitosol 200-T, 300-T m
2
3 3 3
Product parameters (to EnEV [Germany], heating mode without instanta-
neous heating water heater)
Rated output kW 6.1 7.7 9.7
Coefficient of performance
N
at 0 °C/35 °C
4.3 4.3 4.3
Correction factor "0 °C" 1.087 1.087 1.087
Factor Δt = 7 K 0.995 0.987 0.956
Heating energy expendi-
ture value
at 0 °C/35 °C
0.215 0.217 0.221
DHW energy expenditure
value
at 0 °C/35 °C
0.256 0.257 0.262
Specification for 400 V devices (cont.)
225
Specification for 400 V devices
5592 969 GB
Service
Vue de la page 224
1 2 ... 220 221 222 223 224 225 226 227 228 229 230 ... 235 236

Commentaires sur ces manuels