Vitocal 242-G/222-G Type BWT 106 BWT 108 BWT 110
Heat pump performance data
*
1
Heat pump module
Type 200/106 200/108 200/110
Rated output
kW 6.2 7.6 9.7
Refrigerating capacity
kW 4.6 5.7 7.3
Power consumption kW 1.6 1.9 2.4
Coefficient of performance
∊ (COP)
during heating operation
3.9 4.0 4.0
Instantaneous heating
water heater performance
data
Output
kW stepped 2/4/6
Max. output
(with instantaneous heat-
ing water heater)
kW 12.2 13.6 15.7
Brine (primary)
Capacity l 1.6 2.1 2.6
Min. throughput
*
2
l/h 1200 1400 1800
Max. external pressure
drop
mbar 400 480 380
Max. inlet temperature °C 25 25 25
Min. inlet temperature °C –5 –5 –5
Heating water (secondary)
Content, heat pump l 1.6 1.8 2.0
Content, total l 7.0 7.2 7.4
Min. throughput
*
2
l/h 800 800 800
Max. external pressure
drop
mbar 320 320 320
Max. flow temperature °C 60 60 60
Heat transfer medium (only for
the Vitocal 242)
Capacity l 16.0 16.0 16.0
Max. external pressure
drop
mbar 180 180 180
Electrical values
Rated voltage (heat pump) 1/N/PE 230 V/50 Hz
*1
At operating point B0/W35 to EN 255: B0 = Brine inlet temperature 0 °C/W 35 = Heating
water outlet temperature 35 °C.
*1
For further operating points, see datasheet.
*2
Always safeguard the min. throughput.